Verified by manufacturer over a year ago
FR FLOOR 1.5 HR
Retrofit fire collars.
TBA Firefly™ FRF Fire Collars used to fire stop a variety of services which penetrate different Fire Resistant substrates.
For specific applications and FRLs achieved please refer to the referenced Compliance Reports. Must be installed in strict accordance with the construction details contained within the Compliance Reports.
Warringtonfire Report No’s:
FAS190234 RIR
FAS190235 RIR
FAS190236 RIR
TBA Firefly™ retro-fit fire collars are made from steel and high pressure graphite intumescent.
Uniclass | |
NATSPEC National Classification System | 0182 Fire-Stopping |
SpeedSpec | 07810 Fireproofing |
SpecPack | 07810 Fireproofing |
Sizes | 40 mm.50 mm.65 mm.80 mm.100 mm.150 mm. |
Fire resistance level | |
Standard | To AS 1530.4 and AS 4072.1. |
Value | -/90/90. |
Certification | Warringtonfire certified. Guidance for specification option: FAS190234 RIR. FAS190235 RIR. FAS190236 RIR. AS1530.4-2014 certified. AS4072.1-2005 certified. |
Substrates | Concrete. Masonry. Hebel floor. |
Fire rating | 1.5 hour. |
Bonding to substrate | Minimum 120mm thick floor. |
Execution | Manufacturer guidanceDrill a 150 mm Core Hole. Run a 10 mm bead of TBA Firefly Intumastic around the face of the core hole. Then install a TBA Firefly FRF 150 Fire Collar to the underside of the Floor. Fixed using 6 x 40mm long M6 Masonry screws. Gaps around the services filled with TBA Firefly Intumastic HP to the full depth of the fire collar. |