FR FLOOR 1.5 HR

TBA Firefly Variant:

Retrofit fire collars.

Jump to:
+61754114209 Website

Application

TBA Firefly™ FRF Fire Collars used to fire stop a variety of services which penetrate different Fire Resistant substrates.


For specific applications and FRLs achieved please refer to the referenced Compliance Reports. Must be installed in strict accordance with the construction details contained within the Compliance Reports.


Warringtonfire Report No’s:

FAS190234 RIR

FAS190235 RIR

FAS190236 RIR

Description

TBA Firefly™ retro-fit fire collars are made from steel and high pressure graphite intumescent.

General information

Uniclass

Pr_65_52_61_86 Surface-mounted intumescent pipe collarsPrimary

NATSPEC National Classification System

0182 Fire-Stopping

SpeedSpec

07810 Fireproofing

SpecPack

07810 Fireproofing

Specification data - Surface-mounted intumescent pipe collars

Sizes

40 mm.

50 mm.

65 mm.

80 mm.

100 mm.

150 mm.

Fire resistance level

-

Standard

To AS 1530.4 and AS 4072.1.

Value

-/90/90.

Certification

Warringtonfire certified.

Guidance for specification option:

FAS190234 RIR.

FAS190235 RIR.

FAS190236 RIR.

AS1530.4-2014 certified.

AS4072.1-2005 certified.

Substrates

Concrete.

Masonry.

Hebel floor.

Fire rating

1.5 hour.

Bonding to substrate

Minimum 120mm thick floor.

Execution

-

Manufacturer guidance

Drill a 150 mm Core Hole. Run a 10 mm bead of TBA Firefly 

Intumastic around the face of the core hole. Then install a TBA Firefly FRF 150 Fire Collar to the underside of the Floor. Fixed using 6 x 40mm long M6 Masonry screws. Gaps around the services filled with TBA Firefly Intumastic HP to the full depth of the fire collar.