FR WALL 2 HR
Retrofit fire collars.
TBA Firefly™ FRF Fire Collars used to fire stop a variety of services which penetrate different Fire Resistant substrates.
For specific applications and FRLs achieved please refer to the referenced Compliance Reports. Must be installed in strict accordance with the construction details contained within the Compliance Reports.
Warringtonfire Report No’s:
FAS190234 RIR
FAS190235 RIR
FAS190236 RIR
TBA Firefly™ retro-fit fire collars are made from steel and high pressure graphite intumescent.
Uniclass | |
NATSPEC National Classification System | 0182 Fire-Stopping |
SpeedSpec | 07810 Fireproofing |
SpecPack | 07810 Fireproofing |
Sizes | 40 mm.50 mm.65 mm.80 mm.100 mm.150 mm. |
Fire resistance level | |
Standard | To AS 1530.4 and AS 4072.1. |
Value | -/120/120. |
Certification | Warringtonfire certified. Guidance for specification option: FAS190234 RIR. FAS190235 RIR. FAS190236 RIR. AS1530.4-2014 certified. AS4072.1-2005 certified. |
Substrates | Masonry. Concrete block. Hebel blockwall. |
Fire rating | 2 hours. |
Bonding to substrate | Minimum 100mm thick wall. |
Execution | Manufacturer guidanceDrill a 150 mm Core Hole. Run a 10 mm bead of TBA Firefly Intumasic around the face of the core hole. Then install a TBA Firefly FRF 150 Fire Collar to both sides of the wall. Fixed using 6 x 40 mm long M6 Masonry screws. Gaps around the services filled with TBA Firefly Intumasic HP to the full depth of the fire collars |