Fire and smoke curtain.
Suitable for small to medium size openings in both new and existing buildings, such as:
Fyrehalt V is a fire and smoke curtain and with the smallest head box available. It consists of a single overhead coil with no overlap, making it highly reliable. Some of its features include:
Color | Silver |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year |
Uniclass | |
SpecPack | 08330 Roller Shutter Doors 10240 Grilles and Screens |
NATSPEC National Classification System | 0454 Overhead Doors 1002 Fire Services Design and Install |
SpeedSpec | 08330 Roller Shutter Doors |
Performance | |
Fire resistance level | |
Standard | To AS 1530.4. |
Value | -/120/- (minimum).-/120/120 (when used with sprinklers). |
Smoke leakage | |
Standard | To AS 1530.7. |
Value | ≤ 75 m³/h.Manufacturer guidanceTested system is 3.3 x 3.3 m. |
Fire hazard properties | |
Standard | To AS/NZS 1530.3 and AS 3837. |
Group number | 1.Manufacturer guidanceTested in accordance with AS 3837. |
Spread of flame index | Manufacturer guidanceTested in accordance with AS 1530.3. |
Durability | 30 000 open-close cycles (minimum). |
Closing time | 150 mm/s (nominal). |
Time delay for deployment | Manufacturer guidanceUpon receipt of alarm or loss of power. |
Time delay for rewind | Manufacturer guidanceUpon reset of the Fire Indicator Panel. |
Fail safe close | Manufacturer guidanceGravity fail safe. |
Curtain | |
Size and shape (maximum) | Manufacturer guidanceAvailable in sizes up to 8 m W x 4 m H. Contact local manufacturer for specific dimension needs. |
Head box | |
Size | 165 mm H x 165 mm D.Manufacturer guidanceWidth varies depending on specified curtain size. Contact local manufacturer for specific dimension needs. |
Side guides | |
Size | 100 mm W x 50 mm D. |
Controls | Control box (290 x 240 x 110 mm).Guidance for specification option: Requires 240 V, 10 A power supply to each box and an alarm signal through a normally closed dry contact. |
Integral accessories | Alarm signal.Guidance for specification option: Should be in the form of a normally closed dry contact. A localised smoke or heat detector may also be used. |
Fire barrier | To AS 1905.2. Manufacturer guidanceRefers to Fire Shutter performance data. |
Box weight | 20 kg/m of system width (for curtain heights up to 3 m). 25 kg/m of system width (for curtain heights up to 4 m). |
MaximumWorkingPressure | 23 Pa (fully closed curtain). Manufacturer guidanceRefers to maximum pressure resistance. |
Optional features | Battery back-up. Rewind switches. Curtain applied signage. Bottom bar covers. |
Installation | To be installed by Smoke Control approved installer network. |
Back support | Masonry. Concrete. Fire rated plasterboard with steel or timber stud. |
Country of product manufacture | Australia |