Verified by manufacturer over a year ago
FR PLASTERBOARD WALLS 2 HR
Passive fire protection.
Intubatt®Intubatt is used to fire stop large holes in floors and walls with or without service penetrations. Also used as a linear gap seal up to 1200mm in height and of infinite length in both walls and floors.
Intubatt® is a high density mineral fibre batt (180 kg/m³ Fire Batt) factory coated on both faces to a precise thickness with a white durable fire resistant mastic.
Material | High density mineral fibre. |
Warranty description | 25 year |
Uniclass | |
NATSPEC National Classification System | 0182 Fire-Stopping |
SpeedSpec | 07810 Fireproofing |
SpecPack | 07810 Fireproofing |
Thickness | 50 mm. |
Fire performance | |
Fire resistance level | |
Standard | To AS 1530.4 and AS 4072.1. |
Value | -/120/120. |
Dimensions | 1200 x 600 x 50 mm. |
Certification | Tested in accordance with AS1530.4·2014. Assessed in accordance with AS4072.1-2005. FAS190234 RIR. Guidance for specification option: Warringtonfire Report. Tested both Horizontally and Vertically. FAS190235 RIR. Guidance for specification option: Warringtonfire Report. Tested both Horizontally and Vertically. FAS190236 RIR. Guidance for specification option: Warringtonfire Report. Tested both Horizontally and Vertically. |
Substrates | FR plasterboard. Guidance for specification option: For wall, floor and ceiling. Hebel powerpanel. Guidance for specification option: For wall. Pronto panel. Guidance for specification option: For wall. Speedpanel. Guidance for specification option: For wall. Block. Guidance for specification option: For wall. |
Fire rating | 2 hours. |
Bonding to substrate | Wall: Minimum 2 x layers of 13 mm FR Plasterboard either side of a steel frame. Guidance for specification option: Minimum 110 mm total wall thickness. |
Use | D1 power cables with tray. Pair coil, flexidrain and cables. Up to 43 mm OD PEX AL gas. NBN triple conduits with cable. ABB IP55 busducts. |