Verified by manufacturer over a year ago
FR PLASTERBOARD WALLS 2 HR
Passive fire protection.
Intubatt®Intubatt is used to fire stop large holes in floors and walls with or without service penetrations. Also used as a linear gap seal up to 1200mm in height and of infinite length in both walls and floors.
Intubatt® is a high density mineral fibre batt (180 kg/m³ Fire Batt) factory coated on both faces to a precise thickness with a white durable fire resistant mastic.
Material | High density mineral fibre. |
Warranty description | 25 year |
Uniclass | |
NATSPEC National Classification System | 0182 Fire-Stopping |
SpeedSpec | 07810 Fireproofing |
SpecPack | 07810 Fireproofing |
Classification data | |
Thickness | 50 mm. |
Fire performance | |
Fire resistance level | |
Standard | To AS 1530.4 and AS 4072.1. |
Value | -/120/120. |
Dimensions | 1200 x 600 x 50 mm. |
Certification | Tested in accordance with AS1530.4·2014. Assessed in accordance with AS4072.1-2005. FAS190234 RIR. Guidance for specification option: Warringtonfire Report. Tested both Horizontally and Vertically. FAS190235 RIR. Guidance for specification option: Warringtonfire Report. Tested both Horizontally and Vertically. FAS190236 RIR. Guidance for specification option: Warringtonfire Report. Tested both Horizontally and Vertically. |
Substrates | FR plasterboard. Guidance for specification option: For wall, floor and ceiling. Hebel powerpanel. Guidance for specification option: For wall. Pronto panel. Guidance for specification option: For wall. Speedpanel. Guidance for specification option: For wall. Block. Guidance for specification option: For wall. Masonry. Guidance for specification option: For wall, floor and ceiling. Concrete. Guidance for specification option: For floor and ceiling. |
Fire rating | 2 hours. |
Bonding to substrate | Wall: Minimum 2 x layers of 13 mm FR Plasterboard either side of a steel frame. Guidance for specification option: Minimum 110 mm total wall thickness. |
Use | D1 power cables with tray. Pair coil, flexidrain and cables. Up to 43 mm OD PEX AL gas. NBN triple conduits with cable. ABB IP55 busducts. Steel universal beams. 150 mm uPVC pipe. up to 300 mm OD steel pipe. |