Verified by manufacturer over a year ago
M400
Smoke containment screen with magnetic sealing.
Suitable for small to medium openings in hospitals and universities. It is the preferred alternative to smoke lobbies.
Smoke Guard M400/M600 is a smoke containment screen which includes magnetic sealing for failsafe occupant egress. Some of its features include:
Color | Silver |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
SpecPack | 08330 Roller Shutter Doors 10240 Grilles and Screens |
NATSPEC National Classification System | 0454 Overhead Doors 1002 Fire Services Design and Install |
SpeedSpec | 08330 Roller Shutter Doors |
Performance | |
Smoke leakage | |
Standard | To AS 1530.7. |
Value | ≤ 9.5 m³/h/m².Guidance for specification option: Tested at 200° C at pressure differential of 20 Pa. Manufacturer guidanceTested system is 1.5 x 3 m. |
Durability | 2000 maintenance-free cycles. |
Closing time | 200 mm/s (nominal). |
Time delay for deployment | Manufacturer guidanceUpon smoke detection by smoke detector or on general alarm. |
Fail safe close | Manufacturer guidanceGravity fail safe. |
Battery back-up | Manufacturer guidanceCan be provided as an optional extra. |
Curtain | |
Size and shape (maximum) | Manufacturer guidanceAvailable in sizes up to 1.52 m W x 3 m H. Heights up to 3.3 m may be possible on a project specific basis. Contact local manufacturer for further details. |
Head box | |
Size | 267 mm H x 230 mm D.Manufacturer guidanceWidth varies depending on specified curtain size. Contact local manufacturer for specific dimension needs. |
Side guides | |
Size | 51 mm W x 13 mm D.51 mm W x 19 mm D.51 mm W x 25 mm D.Manufacturer guidanceDepth is dependent on projection needed to clear lift surround or buttons. |
Controls | Control box.Guidance for specification option: Requires a 240 V, 10 A power supply and an alarm signal through a normally closed dry contact. |
Integral accessories | Alarm signal.Guidance for specification option: Should be in the form of a normally closed dry contact. A localised smoke or heat detector may also be used. Rewind switch. |
Box weight | 45 kg (for opening widths up to 1 m). 60 kg (for opening widths up to 2 m). 75 kg (for opening widths up to 2.3 m). Manufacturer guidanceRefers to system weight. |
MaximumWorkingPressure | 50 Pa (fully closed curtain). Manufacturer guidanceRefers to maximum pressure resistance. |
Optional features | Battery back-up. |
Installation | To be installed by Smoke Control approved installer network. |
Country of product manufacture | Australia |