NBS Source
I'm a manufacturer

Compare variants

FireCurtain FM1 - Vertical Fire Curtain Barrier
FireCurtain FM1 - Vertical Fire Curtain Barrier
FireCurtain FM1 - Vertical Fire Curtain Barrier

Verified 24 days ago

Colt International Ltd

Verified 24 days ago

Colt International Ltd

Verified 24 days ago

Colt International Ltd
Summary
The FireCurtain FM1 is an automatic fire curtain which seals off an area to contain a fire and to prevent that fire from spreading to other areas.
-
-
Application

Suitable for use in fire barrier applications.

-
-
Description

The FireCurtain FM1 is an automatic fire curtain which seals off an area to contain a fire and to prevent that fire from spreading to other areas. The automatic fire curtain has been tested according to multiple standards and also has a CE mark. The specially developed unwinding mechanism is built into the roller and it unrolls in a gravity fail safe manner without needing power.

Features and benefits:

  • Tested in accordance with EN 1634-1.
  • Certified in accordance with EN 16034 and 13241.
  • Classified according to EN 13501-2.
  • Available with two different fire protection fabrics up to EW20 and EW30.
  • Prevents the breakthrough of flames and spread of fire.
  • Width for a single system from 1500–4000 mm.
  • Width for multiple systems up to 9450 mm.
  • Standard drop up to 5500 mm.
  • Installation into a suspended ceiling for "invisible” fire protection.

Dimensions:

The compact modular system is available in the following dimensions:

  • Width for a single system from 1500–4000 mm.
  • Width for multiple systems up to 9450 mm.
  • Standard drop up to 5500 mm.

Drive technology:

The safe operation of an automatic fire curtain is assured: the unwinding mechanisms have different performance classes for all operating modes.

The unwinding mechanism is installed within the roller and contains, in addition to the high-quality DC motor with its planetary gears, a control board with its own intelligence for carrying out the essential safety-related functions:

  • Control of speed.
  • Locking unit.
  • Monitoring of the “rest” position.
  • Synchronisation of multiple units.
  • “HWD” intermediate position when in gravity-fail-safe mode.
  • Adjustment of the bottom bar.
  • More than 10 000 cycles by internal testing.

Classifications:

In accordance with EN 16034 and 13241:

  • Resistance tests to fire done for more than 240 minutes (to the standard time/temp curve).
  • Classification in accordance with EN 13501-2: E 60 C/ E 180 C1/ EW 30 C1.
  • Reliability test with 500 cycles.
  • Extra reliability test done to DIN 4102-18 with 10 000 cycles.
  • Self-closing durability: EN 14600, Class C1.

Compliance:

  • Tested and certified to European standard EN 16034 and 13241.
  • Furnace test to EN 1634-1.
  • Classified to EN 13501-2.
  • Fire resistance and integrity: E 180 C.
  • Radiation limitation EW 20 or EW30.
  • Reliability test to EN 16034 & 13241 with 500 cycles.
  • Reliability test to DIN 4102-18 with 10 000 cycles.
  • Manufactured to ISO 9001:2015.
  • Third-party certification (A+) according to APF-1817 and APF-1818 certificates.
-
-
Color
Other
-
-
Finish
Powder-coated
-
-
Material
Glass Fibre, Fabric, Polyurethane, Steel
-
-
Shape
Rectangle
-
-
Length
Bespoke
-
-
Width
Bespoke
-
-
Height
Bespoke
-
-

Specification

Classification data
Standards
-
-
-
Barrier assemblies
To BS 8524-1.
-
-
Test standards
Vertical, horizontal and angled to BS EN 1634-1.
-
-
Third-party certification
CE certified.
-
-
Size
4000 x 3750 mm.
-
-
Performance
-
-
-
Durability class
C2.
-
-
Fire resistance
To EN 13501-2, E 60.
-
-
Reaction to fire
To EN 13501-1, A2-s1,d0.
-
-
Barrier units
Single, SI-N.
-
-
Deployment
Full.
-
-
Activation
SKC-SC control panel.
-
-
Accessories
Hold-open device.
-
-

Additional properties

Bottom bar
Type UK., Type U., Type ID.
-
-

Sustainability data

Material
Glass Fibre, Fabric, Polyurethane, Steel
-
-