NBS Source
I'm a manufacturer

Compare variants

Smokemaster SM5 Automatic Smoke Curtain
Smokemaster SM5 Automatic Smoke Curtain
Smokemaster SM5 Automatic Smoke Curtain

Verified over a year ago

Colt International Ltd

Verified over a year ago

Colt International Ltd

Verified over a year ago

Colt International Ltd
Summary
Automatic smoke curtain preventing the movement of smoke and heat generated by a fire from one area to another by channelling or containing the smoke and heat.
-
-
Application

Typical applications for smoke barriers/ curtains are; smoke reservoir boundaries, channelling screens, void edge screens, void sealing screens, corridor containment, shop unit containment, escalator containment, stairwell containment, and elevator well containment.

Suited to most industrial and commercial buildings.

-
-
Description

Automatic smoke curtain preventing the movement of smoke and heat generated by a fire from one area to another by channelling or containing the smoke and heat.

The smoke curtain has fixing options to suit all types of ceiling configurations and can be integrated into either a suspended or a solid ceiling. It remains hidden until required.


The smoke curtain comprises a flexible heat resistant fabric that is impervious to smoke and hot gases, wound around a circular tube. Upon receiving a signal from the fire detection or on loss of power the curtain automatically unwinds to its operational position.


Smokemaster SM5 smoke curtains are well suited to most industrial and commercial buildings as they are unobtrusive, moving to their active position only when needed.


Features and benefits:

  • High performance: designed to operate for 1000 cycles at normal ambient temperatures in the range 0–60⁰C, and to withstand hot air and smoke at temperatures up to 600⁰C for up to 120 minutes once only.
  • Wide range of options: can be adapted to the physical constraints of the building. All system components can be customized.
  • Certified performance and CE marked.
  • D120 curtain material achieves a resistance to smoke at 600°C for a minimum of 120 minutes.
  • DH120 curtain material achieves a resistance to heat for a period of 120 minutes, following the time-temperature curve in EN 1363-1 with a temperature of 1049°C at the end of the test.
  • All types of material achieve class A2-s1, d0, in accordance with BS EN 13501-1.
-
-
Product certifications
-
-
Material
Glass Fibre
-
-
Shape
Rectangle
-
-
Length
Bespoke
-
-
Width
Bespoke
-
-
Height
Bespoke
-
-

Specification

Classification data
Standard
To BS EN 12101-1.
-
-
Category
ASB2/4.
-
-
Classification categories
D 120.
-
-
Material
D120 stainless steel-reinforced glassfibre.
-
-

Additional properties

Type
SI single roller unit., DH (double horizontal) unit., DV (double vertical) unit.
-
-
Controls
Drive down (D).
-
-
Bottom bar
Bottom bar with weights, galvanized finish., Bottom bar with weights, powder-coated., Bottom bar with weights and spring, galvanized finish., Bottom bar with weights and spring, powder-coated.
-
-
Access panel
Galvanized steel., Powder coated, RAL.
-
-
Headbox
Galvanized steel., Powder coated, RAL.
-
-
Side guides fixing
FR (rollers), end fixed., FR (rollers), face fixed., FR (rollers), flush fixed., FS (loops and rods), end fixed., FS (loops and rods), face fixed., FS (loops and rods), flush fixed.
-
-