NBS Source
I'm a manufacturer

Compare variants

Residual Current Breaker with Over-Current – RCBO – DSE201M – Single Pole
Residual Current Breaker with Over-Current – RCBO – DSE201M – Single Pole
Residual Current Breaker with Over-Current – RCBO – DSE201M – Single Pole

Verified 1 month ago

ABB Ltd

Verified 1 month ago

ABB Ltd

Verified 1 month ago

ABB Ltd
Summary
1P+N eRCBO in one module width with flying neutral lead, suitable for installation in chassis distribution boards.
-
-
Application

Suitable for commercial and industrial applications, providing a breaking capacity of 10 kA and a height of 115 mm.

-
-
Description

1P+N eRCBO in one module width with flying neutral lead, suitable for installation in chassis distribution boards. The presence of a functional earth cable (white) offers additional protection in case of loss of the neutral. The neutral is unswitched.

Provides protection against short-circuit currents, overloads and earth fault currents.

Suitable for commercial and industrial applications, providing a breaking capacity of 10 kA and a height of 115 mm.


Features and benefits:

  • Easy to install: easy and fast wiring operations thanks to the two slots of different dimensions at the line side terminal (bottom): connection possible both with cable and busbars
  • More control in smaller space: space optimization in the panel due to the reduced width and height of the product and straight flying leads instead of pigtail ones.
  • Continuous operation and safety: quick and easy identification of contact status thanks to the CPI window as well as reduced downtime for maintenance thanks to the earth fault indicator.
  • 10 kA, A and AC type.
  • B and C tripping characteristics; rated currents from 6 to 50 A; sensitivity 10, 30, 100, 300 mA.
  • Functional earth white cable is giving additional protection in case of loss of the neutral.
  • Possibility to combine System pro M compact® accessories.
  • Earth fault trip indicator window.


Also available as a 6 kA model, DSE201, for complete protection in residential and light commercial applications. Consult manufacturer for details.

-
-
Color
Grey
-
-
Finish
Smooth
-
-
Shape
Rectangle
-
-
Length
69 mm
-
-
Width
18 mm
-
-
Height
115 mm
-
-
Warranty description
One year
-
-

Specification

Classification data
Standards
To BS EN 61009-1. To IEC 61009-1 and IEC 61009-2-2. TO AS/NZS 61009.
-
-
Operating characteristic
A., AC.
-
-
Tripping characteristic
Type B., Type C.
-
-
Rated current (InA)
6 A., 10 A., 16 A., 20 A., 25 A., 32 A., 40 A., 50 A.
-
-
Rated operational voltage (Ue)
230–240 V a.c.
-
-
Rated impulse withstand voltage (Uimp)
4 kV.
-
-
Rated frequency
50 Hz., 60 Hz.
-
-
Number of poles
One + neutral.
-
-
Rated short circuit capacity (Icn)
10 kA.
-
-
Rated residual operating current
10 mA.
-
-
Features
Blue window fault indication.
-
-
Mounting method
DIN rail.
-
-
Accessories
None., Auxiliary contact., Auxiliary/ Signal contact., Shunt trip., Undervoltage release., Overvoltage release., Bottom fitting auxiliary contact.
-
-

Additional properties

Housing
Insulation group II, RAL 7035.
-
-
Overvoltage
Category III.
-
-
Ingress protection
Housing: IP40.
Terminals: IP20.
-
-
Technical characteristics, other
Insulation voltage: 500 V a.c.
Pollution degree: 2.
Minimum operating voltage for protection against IΔn residual sinusoidal alternating currents: 85 V.
Minimum operating voltage of circuit test: 195 V.
Rated breaking capacity according to IEC 61009: 10 000 A.
Rated breaking capacity according to IEC 60947-2: 15 kA (for 6 A ≤ In ≤40 A); 10 (for In = 50 A).
-
-
Ambient temperature
-25 to +55°C (with daily average ≤35°C).
-
-