NBS Source
I'm a manufacturer

Compare variants

Vigilon Plus - Fire Alarm Panel
Vigilon Plus - Fire Alarm Panel
Vigilon Plus - Fire Alarm Panel

Verified 7 days ago

Gent

Verified 7 days ago

Gent

Verified 7 days ago

Gent
Summary
Honeywell Gent's Vigilon range of fire detection and alarm control panels with intelligent loop powered devices is easy to use and install in all types of buildings.
-
-
Application

Advanced fire detection control panels suitable for buildings of any size.

-
-
Description

Vigilon Plus Control Panels are available in four or six loop variants, each accommodating up to 200 devices per loop, including advanced fire sensors, interfaces, call points, alarm sounders, and visual alarms. The four loop panels are available with integrated 24-hour standby, while the six loop panel offers full 72-hour standby capacity.

Advanced networking options allow networking of up to 200 panels in a multi-domain structure, with copper or fibre optic connections available (Vigilon four and six loop panels only).

Vigilon’s back-lit LCD display presents clear indication of fire or fault location, and the control panel’s innovative 8-line x 40 character display with push-button keypad is simple to use. Fire plans can be tailored to precisely meet site requirements.

Vigilon’s software allows network areas to be sectored to evacuate or alert status or configured with pre-set delays.

Fully compatible with Honeywell Gent’s innovative S-Quad range – a combined Multi-Sensor range with speech, sounder and EN 54-23 Visual Alarm devices in one intelligent unit.

The Vigilon Plus Repeat control panel provides full display and control of the system. Connecting to the detection loop, the repeat panel offers a cost-effective solution with minimal cabling and installation requirements. Repeat panels are supplied with their own 72-hour power supply and standby batteries.

Features and benefits:

  • Integral EN 54-4 PSU and battery standby for 24 hours (four loop).
  • Integral EN 54-4 PSU for 72 hours with external batteries (six loop).
  • Vigilon’s advanced sensing technology and powerful software processing in the panel quickly identifies real fires.
  • PC based commissioning tools allow complex fire plans to be configured.
  • Advanced loop card technology allows for system status monitoring and diagnostics.
  • Loop length up to 2 km.
  • High powered loop capable of support large numbers of Sounders and EN 54-23 VAD's.
  • Compatible with Honeywell Gent Self Testing Sensor Technology.
  • Capable of connecting to Cloud Based Connected Life Safety Systems (CLSS) management system.
  • Extended event log using flash memory card.
  • The control panel has a simple user interface with LCD screen providing accurate information in an emergency.
  • Multiple panel networks can be programmed seamlessly as one system, allowing for flexible design and system management.
  • Flexible programming options are available at the panel.
  • All Vigilon devices connect onto the same two core loop, separate sounder or repeater panel wiring circuits are not required.
  • In the event of a fire or fault, Vigilon’s analogue addressable technology will provide a detailed log of events.
  • PC based Graphics user interface (GUI) available.
  • EN 54-2 and 4 Certified.
-
-
Product certifications
-
-
Color
Black
-
-
Finish
Smooth
-
-
Material
Plastic, Metal
-
-
Shape
Rectangle
-
-
Length
172 mm
-
-
Width
406 mm
-
-
Height
543 mm
-
-
SKU Code
VIGPLUS-24
-
-

Specification

Classification data
Standard
To BS EN 54-2.
-
-
Standby power supply
-
-
-
Standard
To BS EN 54-4.
-
-
Capacity
Battery standby for 24 hours plus 30 minutes in alarm (upgradeable to 72 hours).
-
-
Main display
Monochrome LCD screen (8-line x 40-character display).
-
-
Zone indication
Separate LED mimic diagram.
-
-
Installed capacity
Four loops.
-
-
Monitored sounder circuits (minimum)
Two.
-
-
Printer
20 column printer.
-
-
Indications
Verify, FARE active, FARE fault/disablement, power, fault, disablement, system fault, power fault, sounder, test and delay.
-
-
Controls
Silence alarm, sound alarm, fire reset, cancel buzzer, verify, U1–U4 control keys, menu on/off, 2 x programmable keys, QWERTY keyboard.
-
-
Outputs
Connected Life Safety Services (CLSS) Gateway.
-
-
Input device
Push-button keypad.
-
-
Features
PC based commissioning tools allow complex fire plans to be configured.
-
-
Enclosure
-
-
-
Material
ABS plastics.
-
-
Colour
Black.
-
-
Mounting
Flush mounting with bezel.
-
-

Additional properties

Dimensions
406 x 543 x 172 mm.
-
-
Weight
22 kg.
-
-
Operating temperature
0 to 45ºC.
-
-

Sustainability data

Material
Plastic, Metal
-
-