NBS Source
I'm a manufacturer

Compare variants

Ringmaster AirSeT - Ring Main Unit
Ringmaster AirSeT - Ring Main Unit
Ringmaster AirSeT - Ring Main Unit

Verified 14 days ago

Schneider Electric Ltd

Verified 14 days ago

Schneider Electric Ltd

Verified 14 days ago

Schneider Electric Ltd
Summary
Ring main units with two ring switch disconnectors and circuit breaker.
-
-
Application

Ringmaster AirSeT design is the optimal choice for electrical distribution companies and distribution services, suitable for the following applications:

  • Building and industries.
  • Energy and infrastructure.
  • Mining.
  • Package substation.
-
-
Description

Non-extensible (RN2Air) ring main units with two ring switch disconnectors and circuit breaker in pure air gas filled tank with pressure relief facility.

Features and benefits:

  • IP54 degree of protection of the Ringmaster’s enclosure instead of housing makes it possible to be used in the most aggressive environment.
  • No consideration needs to be taken for an external enclosure, saving cost compared to traditional solutions.
-
-
Color
Grey
-
-
Finish
Smooth
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
1019 mm
-
-
Width
866 mm
-
-
Height
1800 mm
-
-
SKU Code
RN2Air-T1 TLF
-
-

Specification

Classification data
Standard
To IEC 62271-1, IEC 62271-200 and IEC 62271-201.
-
-
Third-party certification
To ENA TS 41-41.
-
-
Internal arc classification
To IEC 62271-200, Class AF.
-
-
Mounting arrangement
Transformer-mounted., Free-standing.
-
-
Switchgear arrangement
Non-extensible.
-
-
Rated voltage (Ur)
12 kV.
-
-
Rated frequency
50 Hz.
-
-
Number of phases
Three.
-
-
Rated insulation levels
-
-
-
Rated short-duration power frequency withstand voltage (Ud)
28 kV for one minute., 38 kV for one minute.
-
-
Rated lightning impulse withstand voltage (Up)
75 kV phase-to-phase, phase-to-earth., 95 kV phase-to-phase, phase-to-earth.
-
-
Rated short-time withstand current (Ik)
21 kA for three seconds.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
To BS EN 60529, IP54.
-
-
Mechanical protection (minimum)
IK10.
-
-
Colour
Grey.
-
-
Cable entry
Direct coupling to transformer., Free-standing.
-
-
Dimensions
-
-
-
Width (maximum)
890 mm.
-
-
Height (maximum)
1810 mm.
-
-
Depth (maximum)
920 mm.
-
-
Busbars
-
-
-
Material
Bare copper.
-
-
Rated continuous current (Ir)
200 A., 630 A.
-
-
Ring switches
-
-
-
Standard
To IEC 62271-102 and IEC 62271-103.
-
-
Format
SF6-free, circuit breaker earth switch.
-
-
Rated continuous current (Ir)
630 A.
-
-
Rated short circuit making current (Ima)
52.5 kA.
-
-
Switch class
E2.
-
-
Operating mechanism
Independent manual., Motor operated.
-
-
Circuit breaker
-
-
-
Standard
To IEC 62271-100.
-
-
Format
SF6-free, circuit breaker earth switch.
-
-
Method of installation
Fixed.
-
-
Rated continuous current (Ir)
200 A.
-
-
Rated short circuit breaking current (Isc)
21 kA.
-
-
Rated short circuit making current (Ima)
52.25 kA.
-
-
Rated operating sequence
O – 3 min – CO – 3 min – CO.
-
-
Circuit breaker class
E2.
-
-
Operating mechanism
Independent manual., Motor operated.
-
-

Additional properties

Protection
Time Limit Fuse (TLF).
-
-
Indication
Pure air gauge, mechanism ON/OFF, mechanism EARTH/MAIN, on-off push button.
-
-
Model
RN2Air-T1 TLF.
-
-

Sustainability data

Material
Metal
-
-