NBS Source
I'm a manufacturer

Compare variants

UG - gaSteam - Gas-Fired Steam Humidifier Range
UG - gaSteam - Gas-Fired Steam Humidifier Range
UG - gaSteam - Gas-Fired Steam Humidifier Range

Verified 3 months ago

CAREL

Verified 3 months ago

CAREL

Verified 3 months ago

CAREL
Summary
Range of humidifiers running on natural gas, a clean, sustainable and economical source of energy. It produces steam from both mains water and demineralized water.
Third party certification
Digital objects
-
-
Color
White
-
-
Finish
Galvanized
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
1443 mm, 1560 mm, 1620 mm
-
-
Width
656 mm, 800 mm, 993 mm, 1107 mm, 1668 mm
-
-
Height
1603 mm
-
-
Warranty description
Two year
-
-

Specification

Electrical supply type
Single phase, 230 V a.c., 50 Hz (D005)., Single phase, 115 V a.c., 60 Hz (D105).
-
-
Steam source
Gas fired.
-
-
Material
Stainless steel.
-
-
Access doors for maintenance
Manufacturer's standard.
-
-
Accessories
None., DP/*R0 lance for duct (standard)., DP/*RU lance for duct (high capacity)., DP/*RH lance for duct (high efficiency)., Hoses., Probe - DPW* wall sensor., Probe - DPP* sensor for industrial environments., Probe - DPD* duct sensor., Probe - ASET* temperature sensor for steam baths.
-
-

Additional properties

Model
Indoor; 1–45°C (H).
-
-
Dimensions
1443 x 656 x 1603 mm.
-
-
Weight
240 kg.
-
-
Network type
Modbus®., BacNET., Modbus Ethernet., BacNET Ethernet.
-
-
Steam
Rated production: 45 kg/h.
Steam production modulation: 25–100%.
-
-
Power consumption
180 W at rated voltage.
-
-
Connections
Steam: 1 x 80 mm diameter.
Gas: 1 x 1"G.
Water fill: 1 x ¾"G male.
Water drain: 1 x 50 mm diameter.
Exhaust flue: 1 x 80 mm diameter.
Flue connection: 1 x 80 mm diameter.
-
-
Pressure
Steam outlet pressure limits: 0–2000 Pa (0–0.3 psi).
-
-
Conditions
Operating: 1 to 40°C, 10–60% relative humidity.
Storage: -10 to 70°C, 5–95% relative humidity.
-
-
Water
Fill:
· Temperature limits, indoor operating conditions: 1 to 40°C; outdoor operating conditions: -40 to 45°C.
· Water pressure limits: 0.1 to 0.8 MPa (1 to 8 bar).
· Instant flow rate: 18 L/m.
· Total hardness: 4 to 40°fH.
· Conductivity limits: 1500 μS/cm.
Drain:
· Temperature: <100°C.
· Instant flow rate: 32 L/m.
-
-
Fuel
Natural gas., LPG.
-
-
Heat
Gross input: 34.8 kW.
Net output: 33 kW.
-
-
Ingress protection
IP20.
-
-
Controller
Continuous modulation: 25–100%.
Built-in control: rH or temperature (probes not included).
Proportional to external signal: Yes.
Limit probe: Yes.
Remote ON/OFF: Yes.
Alarm relay: Yes.
Signal type (probe or external controller): 0–10 V; 0–1 V; 2–10 V; 0–20 mA; 4–20 mA.
Supervisor (via RS485 and Ethernet): Yes.
-
-
Gas
Flue gas flow-rate (natural gas G20): 0.0163 kg/s.
Flue gas temperature (natural gas G20): 135°C.
NOx emissions class: 5.
-
-
Third-party certification
CE; ETL (UL998); TÜV and AGA.
-
-