Ductile iron fixed integral orifice, double regulating valve.
-
-
Application
Primarily used in injection or other circuits requiring a double regulating valve for system balancing.
Suitable for flow regulation and isolation.
Supplied with Fig. 631 test points to enable flow measurement.
-
-
Description
Ductile iron fixed integral orifice, double regulating valve with ANSI version option MHA739.
Features and benefits:
Single unit Y-Pattern globe valves incorporating an integral orifice plate, to form a fixed orifice flow measurement unit with regulation and isolation capacity.
The Double Regulating feature allows the valve to be used for isolation and to be reopened to its pre-set position, to maintain required flow rate.
Accuracy of flow measurement is ±5% at all open positions of the valve, in accordance with BS 7350: 1990.
Primarily used in injection or other circuits requiring a double regulating valve for system balancing.
External spray epoxy coated for improved durability.
Supplied with Fig. 631 test points to enable flow measurement.
Valve operation by means of a hand wheel.
-
-
Color
Blue, Silver, Red, Yellow
-
-
Material
Bronze, Rubber, Brass, Stainless steel, Steel, Cast iron, Iron
-
-
SKU Code
MH739, MHA739
-
-
Specification
Classification data
Standard
To BS 7350.
-
-
Arrangement
Globe (Y-pattern).
-
-
Material
Body and bonnet: Ductile iron, Disc: EPDM coated cast iron, Disc bush and seat ring: Bronze, Stem: Stainless steel grade 410 – 1.4006, Packing and bonnet gasket: Non-asbestos, Gland (65 to 150 mm): Brass CW614N, Gland (200 to 300 mm): Cast iron.
-
-
Connections
Flanged to BS EN 1092-2, PN16 and Flanged to ANSI B16.1, Class 125.
-
-
Additional properties
PressureRange
Temperature: -10 to +120°C: PN16.
-
-
Inlets/outlets diameter
DN65.
-
-
Dimensions
290 x 262 mm.
-
-
Weight
16.3 kg.
-
-
Flow capacity
93 (Kv), 90 (Kvs).
-
-
PressureLossCoefficient
6.9.
-
-
Integral accessories
Fig. 631 test points.
-
-
Sustainability data
Material
Bronze, Rubber, Brass, Stainless steel, Steel, Cast iron, Iron