NBS Source
I'm a manufacturer
Compare variants

Analogue Addressable Manual Call Points - Analogue Addressable Manual Call Points

Verified by manufacturer 7 days ago

MCP - resettable element and protective cover - IP43

Gent Variant:
Product certifications:
  • LPCB Certification

    LPCB Certification

    Certificate type

Manual call points for the Vigilon and Nano system are easy to install and can be mounted on standard installation back boxes or bespoke red back boxes for surface or semi-recessed mounting.

Jump to:
+44 (0) 203 4091779 Website

Application

Manual call points suitable for surface or semi-recessed mounting in internal environments, with an IP67-rated version available for external applications in all building types.

Description

Every manual call point is continuously monitored ensuring a trigger is responded to in less than one second system wide.

The range includes options for glass and resettable elements and lift-up protective covers.

An environmentally protected (EP) version with Ingress protection rating IP67 is also available, complete with resettable element, protective cover and backbox.

Features and benefits:

  • Resettable elements.
  • Lift up protective covers.
  • Weatherproof version (IP67) suitable for external areas.
  • Up to 200 per loop.
  • Integral short-circuit isolator.
  • Surface or semi-flush options.
  • Certified to EN 54 part 11 and 17.

General information

Color

Red

Finish

Smooth

Material

Plastic

Shape

Square

Length

30 mm

Guidance for specification option:

EP with protective cover.

Width

90 mm

Height

90 mm

Uniclass

Pr_75_80_30_50 Manual call pointsPrimary

CAWS

W90/336 Manual call points

SKU Code

S4-34845

Specification data - Manual call points

Classification data

Standard

To BS EN 54-11.

Manufacturer guidance

To BS EN 54-17.

Third-party certification

LPCB-approved.

Designation

Type B.

Frangible element

Resettable.

Integral red visual indicator

Required.

Environmental category

Indoor.

Mounting

Surface.
Semi-recessed.

Protective covers

Required.

Power source

Loop powered.

Ingress protection

IP43.

Dimensions

90 x 90 x 30 mm.

Weight

0.11 kg.

Manufacturer guidance

Approximate.

Operating temperature

-25ºC to 70ºC.

Integral accessories

Not applicable.

Sustainability data

Material

Plastic

Product certifications

LPCB Certification

LPCB Certification

Honeywell Gent S4-34845, S4-34805-EP, S4-34895 EN54-11 Certificate of Approval

Literature

Honeywell Gent Manual Call Points

Honeywell Gent Manual Call Points

Honeywell Gent S4-348xx Honeywell Gent Manual Call Point Installation Manual

Honeywell Gent S4-348xx Honeywell Gent Manual Call Point Installation Manual

Honeywell Gent Key switch Manual Call Point Installation Instructions

Honeywell Gent Key switch Manual Call Point Installation Instructions

Honeywell Gent S4-34805-EP, Environmentally Protected Manual Call Point Installation Instructions

Honeywell Gent S4-34805-EP, Environmentally Protected Manual Call Point Installation Instructions

Honeywell Gent Vigilon Plus Control Panels

Honeywell Gent Vigilon Plus Control Panels