Verified by manufacturer 6 days ago
XCL-LB-CH4-RA (flammable gas - analogue)
Large bore aspirating gas detector which provides reliable detection of gases for occupant protection and process monitoring using Aspirating Detection Pipework Network.
Suitable for a range of application areas, for example:
Large bore aspirating gas detector which provides reliable detection of gases for occupant protection and process monitoring.
This configuration utilizes the aspirating smoke detection (ASD) pipe networks (25 mm/ 27 mm OD) to deliver gas detection via multiple hole (multi-point) sampling. The combined solution also provides protection against fire threats.
The VESDA Sensepoint XCL – Large Bore portfolio has a range of gas sensors that addresses a wide range of applications, and through its Bluetooth interface can be paired with a smart devices for commissioning and maintenance. The smart device application (Sensepoint App) provides quick access to detector diagnostic information and simplifies detector configuration, calibration and bump testing.
Features and benefits:
Color | Black |
Material | Polycarbonate |
Shape | Square |
Length | 59 mm Manufacturer guidanceDepth. |
Width | 113 mm |
Height | 113 mm |
Warranty description | One year Guidance for specification option: 12 months from date of shipment. |
Uniclass | |
CAWS | W90/331 Carbon monoxide alarms |
SKU Code | XCL-LB-CH4-RA |
Classification data | |
Standards | |
Functional safety | To BS EN 50270. |
Detector type | Multi-point. |
Gas | Flammable (CAT). Guidance for specification option: 20–100% LEL. |
Ingress protection (minimum) | IP65. |
Display type | Light-emitting diode display (LED). |
Outputs | 4–20 mA analogue. |
Relay type | 2 no. 5 A/ 24 V d.c. programmable relays. |
Third-party certification | EN/ UL/ IEC 61010-1, CSA-C22.2 No. 61010-1-12, RED, FCC, BT SIG, UL 2075 (CO and CH4), AS 1668.2. |
Power supply | 24 V d.c. |
Weight | 500 g. |
Power consumption | <1.7 W. |
Operating temperature | -20 to +50°C. |
Operating humidity | 0–99% RH, non-condensing. |
AtmosphericPressure | 90–110 kPa. |
Cable | Gauge: 0.5–1 mm². Guidance for specification option: Pluggable rising clamp style. |
Accessories | Not required. XCL-LB-CAP - Flow Cap. XCL-LB-ELB - 60° Elbows. XCL-M20-CG - Cable Glands. XCL-LB-FLT-1 - Filter (CAT, NH3, CO2). XCL-LB-COV-1 - Sensor Cover (CAT, NH3, CO2). |
Material | Polycarbonate |
XTRALIS Aspirating Gas Detector - VESDA Sensepoint XCL Large Bore
XTRALIS VESDA Sense point Gas Detection FAQ's
XTRALIS VESDA Sensepoint XCL Large Bore Gas Detection For ASD Pipework Engineering Specification
XTRALIS VESDA Sensepoint XCL ASD Gas Detection - Installation Manual
XTRALIS VESDA Senspoint XCL Large Bore ASD gas detection Battery Room Application Guide
XTRALIS VESDA Senspoint XCL Large Bore ASD gas detection Cable tunnel Application Guide
XTRALIS VESDA Senspoint XCL Large Bore ASD gas detection Plant Room Application Guide
XTRALIS VESDA Senspoint XCL Large Bore ASD gas detection Metro Tunnel Application Guide
XTRALIS VESDA Senspoint XCL Large Bore ASD gas detection Car Park Application Guide