Verified by manufacturer 5 days ago
ATICS-2-63A-DIO
CE Marking
Certificate type
Transfer switching device for safety-relevant and medical locations.
For safety-relevant environments, including:
The ATICS® transfer switching devices provide all functions for changeover between two independent power supplies. The integration of both the electronic system and the switching elements in one flat, compact device reduces space requirements in the switchgear cabinet, minimises the amount of wiring, and reduces the fault probability. For maximum reliability, ATICS® was designed in accordance with the guidelines for functional safety.
Connectors at all connecting wires in combination with bypass switches enable ATICS® to be tested during ongoing operation. In case of need for service, it is possible to repair or replace the device without interrupting the power supply. ATICS® considerably enhances the safety level in industry and other sensitive environments like hospitals.
Features and benefits:
Suitable for space-saving installation/retrofitting:
Convenient installation and commissioning:
Safe operation:
Uninterrupted maintenance:
Applications:
Color | Yellow |
Material | Polycarbonate |
Shape | Other |
Length | 340 mm 234 mm |
Width | 73.5 mm 75 mm |
Height | 263 mm |
Warranty description | Two year |
Uniclass |
Standards | To DIN VDE 0100-710, DIN VDE 0100-718, ÖVE/ÖNORM E 8007, IEC 60364-7-710, DIN EN 61508-1, IEC 61508-1, DIN EN 61508-2, IEC 61508-2, DIN EN 61508-3, IEC 61508-3, DIN EN 60947-6-1, IEC 60947-6-1. |
Method of controlling transfer | Automatic.Guidance for specification option: Manual operation also possible as failsafe backup. |
Operating sequence | I-O-II. |
Rated operational voltage (Ue) | 230 V. |
Rated insulation voltage (Ui) | 250 V. |
Rated operational current (Ie) | 63 A. |
Utilization category | Manufacturer guidanceConsult manufacturer's literature for details and insert requirements. |
Rated operational frequency | 50 Hz, 60 Hz. |
Number of poles | Two. |
Terminals | Screw-type terminals. |
Controls | |
Type | Integral to switch. |
Display type | Liquid crystal display (LCD). |
Illuminated display to indicate the following conditions | Line 1: Measured values of mains voltage and frequency; Switch position of the automatic transfer switching device; Line 2: Measured values of mains voltage and frequency; Display of the load in the IT system in %. |
User-adjustable functions | Changeover; Voltage; Current; Relay; Digital input; Data logger; Language; Interface; Clock; Password.Manufacturer guidanceSee tables in sections 4.1 to 4.10 of ATICS-...-DIO checklist document for details. |
Features | Autom. changeover test; Manual changeover test; Last changeover test; Generator test; Test communication. |
Enclosure | |
Ingress protection (minimum) | To DIN EN 60529, IP40. |
Material | Polycarbonate. |
Colour | Yellow. |
Accessories | ATICS-BP-2-63A-SET Bypass switch set. Guidance for specification option: Rated operational current Ie: 63 A a.c. Scope of delivery: Bridge, terminal cover, auxiliary contacts, LEDs green/red. |
Country of product manufacture | Germany |
Material | Polycarbonate |
Recyclability | Can be returned to manufacturer for disposal under WEEE regulations. |