ADVANTAGE MP 1V120 smoke control shutter
DoP
Certificate type
UK Conformity Assessed (UKCA)
Certificate type
Classification report acc. to EN 13501-4
Certificate type
Certificate of Compliance
Certificate type
Automatic (AOV) Rectangular EIS smoke control damper (SCD) -fire resistance up to 120 minutes- AA, Multi, C10.000, shaft installation c/w. grille, including aesthetical, architectural design option
AVANTAGE MP - Automatic Smoke Control Damper (AOV) - 60-90-120 minutes, with "aesthetic design" grille option
Automatic (AOV) Rectangular EIS smoke control damper (SCD) -fire resistance up to 120 minutes- AA, Multi, C10.000, shaft installation
c/w. grille, including aesthetical, architectural design option
Avantage MP Certified installations and sealing methods
Avantage MP Fields of application
Avantage MP Building applications:
AVANTAGE MP - Automatic Smoke Control Damper (AOV) - 60-90-120 minutes, with "aesthetic design" grille option
Automatic (AOV) Rectangular EIS smoke control damper (SCD) -fire resistance up to 120 minutes- AA, Multi, C10.000, shaft installation
c/w. grille, including aesthetical, architectural design option
Avantage MP Distinct Product Features
(incl. specifications)
Avantage MP Installer & User Benefits:
Avantage MP Range: (Width/Height)
Avantage MP Aesthetical Grille Option:
Notes:
Color | Silver Other Guidance for specification option: Choice of colour (RAL). |
Finish | Natural |
Material | Aluminium |
Shape | Rectangle |
Length | 250 mm Guidance for specification option: Depth. |
Width | 350 mm 400 mm 450 mm 500 mm 550 mm Manufacturer guidanceNominal. |
Height | 385 mm 415 mm 445 mm 475 mm 505 mm Manufacturer guidanceNominal. |
Warranty description | One year |
Uniclass | |
CAWS | U90/445 Dampers, smoke |
Standard | To EN 12101-8:2011. |
Classification | |
Standard | To EN 13501-4. |
Multi-compartment | |
Integrity class | EI 90.Guidance for specification option: Minimum. EI 120.Guidance for specification option: Consult manufacturer for installation requirements on how to achieve classification. |
Suitability | Ve duct. |
Smoke leakage | S. |
Under pressures | 1500. |
Inside or outside | (i ↔ o). |
Smoke control use | C10000. |
Activation | AA – automatic. |
Actuators | Motorized - drive open & close, 24 V d.c.Guidance for specification option: -10/ +15%. Motorized - drive open & close, 48 V d.c.Guidance for specification option: -10/ +15%. Not required (manual).Guidance for specification option: Key provided. |
Dimensions | Guidance for specification option: Consult manufacturer's literature for performance details and insert requirements:
Overall height = nominal height + 54 mm. Overall width = nominal width + 54 mm. Consult manufacturer unit weights based on requirements (10.1–31.7 kg). |
Accessories | VD24 - natural magnet 24 V DC. FDCU - Limit switch (open/ closed). EASY-KAP ME/MP - mounting frame. EASY-KGC ME/MP 1V - mounting frame with hinged drop guard grid. TL - trailing lead 3 m for external connection. |
Third-party certification | CE marked EFECTIS_1812_CPR_1830. |