Verified by manufacturer 6 days ago
LPCB Certification
Certificate type
Honeywell Gents Vigilon range of fire detection and alarm control panels with intelligent loop powered devices is easy to use and install in all types of buildings.
Advanced fire detection control panel suitable for buildings of any size.
The Compact Plus 2 loop panel accommodates up to 200 devices including advanced fire sensors, interfaces, call points, alarm sounders, and visual alarms. It features integrated 24-hour standby capacity and provides a clear, back-lit LCD display indicating Fire or Fault location. The innovative 8-line x 40 character display with push-button keypad ensures simple operation. Fire plans can be tailored to precisely meet site requirements.
The panel is fully compatible with Honeywell Gent’s S-Quad range – a combined Multi-Sensor range with speech, sounder, and EN54-23 visual alarm devices in one intelligent unit.
Features and benefits:
Color | Black |
Finish | Smooth |
Material | Plastic Metal |
Shape | Rectangle |
Length | 101 mm |
Width | 338 mm |
Height | 403 mm |
Uniclass | |
CAWS | S92/420 Alarm devices S92/420 Alarm devices W90/120 Fire detection and alarm systems in domestic premises W90/325 Fire detection and alarm control and indicating equipment W90/125 Fire detection and alarm systems in non-domestic premises |
Classification data | |
Standard | To BS EN 54-2. |
Standby power supply | |
Standard | To BS EN 54-4. |
Capacity | Battery standby for 24 hours plus 30 minutes in alarm. Guidance for specification option: 2 x 12Ah batteries. |
Main display | Monochrome LCD screen (8-line x 40-character display). |
Zone indication | 32 zonal LED indicators. Guidance for specification option: Up to 32 'Secret until lit' LED display. Extended zonal indication can be provided with an external mimic panel. |
Installed capacity | Two loops. Guidance for specification option: 200 with alarm current 800 mA (max alarm current across both loops (1.2 A). |
Monitored sounder circuits (minimum) | Two. |
Printer | Not required. Guidance for specification option: No printer as standard, but external can be added. |
Indications | Verify, FARE active, FARE fault/disablement, power, fault, disablement , system fault, power fault, sounder, test and delay. |
Controls | Silence alarm, sound alarm, fire reset, cancel buzzer, verify, U1–U4 control keys, menu on/off, 2 x programmable keys, QWERTY keyboard. |
Outputs | Output to fire alarm devices. Guidance for specification option:
|
Input device | Push-button keypad. |
Features | PC based commissioning tools allow complex fire plans to be configured. |
Enclosure | |
Material | ABS plastics. |
Colour | Black. |
Mounting | Flush mounting with recessing bezel. |
Dimensions | 338 x 403 x 101 mm. Manufacturer guidanceW x H x D. |
Weight | 12 kg. |
Operating temperature | 0 to 45ºC. |
Material | Plastic Metal |