Verified by manufacturer 11 months ago
Standard frame
Class A rain defence louvres with vertical blades and visible mullions, offering maximum protection against wind-driven rain penetration and excellent airflow. Classified as A 1 up to 3.5 m/s.
Rain defence louvres.
Class A rain defence louvres with vertical blades and visible mullions, offering maximum protection against wind-driven rain penetration and excellent airflow. Classified as A 1 up to 3.5 m/s.
Features and benefits:
Color | Silver Other |
Finish | Mill Anodized Powder-coated |
Material | Aluminium |
Length | 131 mm Guidance for specification option: Unit depth, standard section on elevation. Glazing frame variants are 133 mm deep. |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/54 Louvres L10/650 Metal louvres H11/140 Louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert requirements or insert As drawing or As schedule. Unit depth: 131 mm. Combine units to suit any requirements. |
Material | All components to be one-piece members extruded from aluminium alloy 6063-T6, minimum nominal thickness to be: 3.18 mm for jambs & mullions, 2.03 mm for heads & cills and 1.52 mm for blades. |
Finish | Milled.Anodized, clear.Anodized, colour.Guidance for specification option: Insert colour requirements. Polyester powder-coated finish, matt, colour.Guidance for specification option: Insert colour requirements. Standard for polyester powder-coated finishes. 30 gloss units. Polyester powder-coated finish, gloss, colour.Guidance for specification option: Insert colour requirements. 70 gloss units. |
Colour | As Finish. |
Construction | Supplied as modules, mechanically assembled in the factory using stainless steel fasteners. Multiple module installations to include interlocking visible mullions with drainage channels.Guidance for specification option: Invisible joint detail can be achieved if required. Contact manufacturer for details. |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class A up to 3.5 m/s. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 1: Airflow coefficient Ce (entry): 0.466; Cd (discharge): 0.421.Guidance for specification option: K factor (entry/ discharge): 4.605/ 5.642. |
Louvre configuration | |
Number of banks | One. |
Blade orientation | Vertical. |
Blade pitch | 25 mm. |
Blade angle | Complex extruded blade profile. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
Dampers, high-performance PVC-U, volume control.Guidance for specification option: Insert requirements.
Dampers, aluminium, volume control.Guidance for specification option: Insert requirements.
Snap-on cover plate to close-off louvre frame.Guidance for specification option: Used to close off head frame, cill frame and/or jamb. Insert requirements. |
Cill pan | Louvres to be supplied with a full depth cill pan with welded side panels, formed from 2 mm-thick aluminium. Guidance for specification option: Size to suit project requirements; consult manufacturer for details. |
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. |
Blast resistance | Required. Guidance for specification option: Can withstand up to 86.87 kPa blast pressure at an impulse of 536.41 kPa/m²·ms. Not required. |
Material | Aluminium |