Verified by manufacturer 10 months ago
Standard frame, visible mullions
Modular ventilation louvres offering very good airflow and some rain defence.
Ventilation louvres providing very good airflow and some rain defence.
Modular ventilation louvres offering very good airflow and some rain defence. Classified as C 2 up to 1.0 m/s.
Features and benefits:
Color | Silver Other |
Finish | Mill Anodized Powder-coated |
Material | Aluminium |
Length | 102 mm Guidance for specification option: Unit depth, visible mullions. 154 mm Guidance for specification option: Unit depth, hidden mullions. 108 mm Guidance for specification option: Unit depth, glazing frame option. |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/54 Louvres L10/650 Metal louvres H11/140 Louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert length and width requirements or insert As drawing or As schedule. Combine units to suit any requirements. Unit depth: 102 mm. |
Material | All components to be one-piece members extruded from aluminium alloy 6063-T6 (nominal minimum thickness to be: 1.73 mm for blades, 2.05 mm for heads, cills, jambs & mullions). |
Finish | Milled.Anodized, clear.Anodized, colour.Guidance for specification option: Insert colour requirements. Polyester powder-coated finish, matt, colour.Guidance for specification option: Insert colour requirements. Standard for polyester powder-coated finishes. 30 gloss units. Polyester powder-coated finish, gloss, colour.Guidance for specification option: Insert colour requirements. 70 gloss units. |
Colour | As Finish. |
Construction | Supplied as modules, mechanically assembled in the factory using stainless steel fasteners. Multiple module installations to include interlocking visible mullions. |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class C up to 1.0 m/s.Guidance for specification option: Class D at 1.5–3.5 m/s. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 2: Airflow coefficient Ce (entry): 0.338; Cd (discharge): 0.345.Guidance for specification option: K factor (entry/ discharge): 8.753/ 8.402. |
Louvre configuration | |
Number of banks | One. |
Blade orientation | Horizontal. |
Blade pitch | 100 mm. |
Blade angle | 38°. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
Dampers, high-performance PVC-U, volume control.Guidance for specification option: Insert requirements.
Dampers, aluminium, volume control.Guidance for specification option: Insert requirements.
|
Cill pan | Not required. Louvres to be supplied with a full depth cill pan with welded side panels, formed from 2 mm-thick aluminium. Guidance for specification option: Size to suit project requirements; consult manufacturer for details. |
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. |
Material | Aluminium |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |
CS Louvres - Architectural Line Louvres - Double-Bank Architectural Louvres
CS Louvres - Screening Louvres - Visual Screening Louvres
CS Louvres Rain Defence Louvre B-7505 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre PL-5700 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5605 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5900 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSH-5700AL - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSV-5700 - Class A Rain Defence Louvres
CS Louvres Ventilation Louvre A-3105 - Modular Ventilation Louvres
CS Louvres Ventilation Louvre A-3105C - Continuous Line Ventilation Louvres