Verified by manufacturer 10 months ago
Standard frame
Perform™ ventilation louvres with horizontal blades concealed behind an attractive perforated skin. Offers good airflow and weather performance. Classified as C 3 up to 3.0 m/s.
Ventilation louvres proving good airflow and weather performance.
Perform™ ventilation louvres with horizontal blades concealed behind an attractive perforated skin. Offers good airflow and weather performance. Classified as C 3 up to 3.0 m/s.
Features and benefits:
Color | Silver Other |
Finish | Mill Anodized Powder-coated |
Material | Aluminium |
Length | 191 mm Manufacturer guidanceLouvre depth inc. perforated screen. |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/54 Louvres L10/650 Metal louvres H11/140 Louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert requirements or insert As drawing or As schedule. Unit depth: 191 mm. Combine units to suit any requirements. |
Material | Perforated sheet: 3 mm-thick, aluminium alloy 1050 H14/H24 as standard. All other components to be one-piece members extruded from aluminium alloy 6063-T6(nominal minimum thickness to be 1.73 mm & 1.98 mm for blades, 2.54 mm for heads, cills, jambs & mullions). |
Finish | Mill finish perforated screen/ matt black louvre.Anodized (clear) perforated screen/ matt black louvre.Anodized (colour) perforated screen/ matt black louvre.Guidance for specification option: Insert colour requirements. PPC (matt), colour perforated screen/ matt black louvre.Guidance for specification option: Insert colour requirements. Standard for polyester powder-coated finishes. 30 gloss units. PPC (gloss), colour perforated screen/ matt black louvre.Guidance for specification option: Insert colour requirements. 70 gloss units. |
Colour | As Finish. |
Construction | Supplied as modules, mechanically assembled using stainless steel fasteners.Guidance for specification option:
Other perforation screen options can be supplied but may be subject to additional testing to establish airflow and rain defence performance). |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class C up to 3.0 m/s.Guidance for specification option: Class B at 0.00 m/s; Class D at 3.5 m/s. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 3: Airflow coefficient Ce (entry): 0.260; Cd (discharge): 0.253.Guidance for specification option: K factor (entry/ discharge): 14.793/ 15.623. |
Louvre configuration | |
Number of banks | One. |
Blade orientation | Horizontal. |
Blade pitch | 100 mm. |
Blade angle | 38°. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request.
As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included.
As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
Dampers, high-performance PVC-U, volume control.Guidance for specification option: Insert requirements.
Dampers, aluminium, volume control.Guidance for specification option: Insert requirements.
Snap-on cover plate to close-off louvre frame.Guidance for specification option: Used to close off head frame, cill frame and/or jamb. Insert requirements. |
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. |
Material | Aluminium |
CS Louvres - Architectural Line Louvres - Double-Bank Architectural Louvres
CS Louvres - Screening Louvres - Visual Screening Louvres
CS Louvres Rain Defence Louvre B-7505 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre PL-5700 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5605 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5900 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSH-5700AL - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSV-5700 - Class A Rain Defence Louvres
CS Louvres Ventilation Louvre A-3105 - Modular Ventilation Louvres
CS Louvres Ventilation Louvre A-3105C - Continuous Line Ventilation Louvres