Verified by manufacturer today
PPFC120– Standard Model, Constant Air Volume
A metal-free, corrosion-proof fume extraction solution built from medical-grade welded polypropylene and designed for complex, chemical-intensive applications.
The ducted fume cupboard is designed for use with corrosive acidic compounds such as hydrofluoric, sulfuric and nitric acid. The polypropylene build material prevents surface degradation and rust, increasing product longevity and minimising maintenance costs.
It's suitable for the pharmaceutical, chemical, healthcare, higher education and life sciences industries, providing a balance between versatility and protection. Common applications include:
The ducted fume cupboard is a self-contained fume extraction system designed to prevent exposure to aerosols, vapours, gases and particulates generated during chemical experiments. It uses PVC (or polypropylene) ductwork connected to a roof-mounted ventilation stack to exhaust fumes into the atmosphere. Compatible with both CAV (constant air volume) and VAV (variable air volume) extraction control types, it's a customisable product that can be tailored to the client's requirements.
Features and benefits:
Color | White |
Finish | Other |
Material | Polypropylene |
Shape | Rectangle |
Length | 1200 mm 1500 mm 1800 mm 2000 mm 2500 mm |
Width | 830 mm Bespoke |
Height | 2320 mm Bespoke |
Warranty description | One year |
Uniclass |
SKU Code | PPFC120, PPFC150, PPFC180, PPFC2000, PPFC2500 |
Classification data | |
Standard | To EN 14175. |
Arrangement | Free standing unit. |
Special requirements | Acid-based processes. |
Extract air | |
Face velocity | 0.5 ±0.1 m/s (100 ±20 FPM). |
Operation | Continuous. |
Materials | Polypropylene. |
Sash | |
Sash arrangement | Horizontal. |
Operation | Manual. |
Maximum operational sash opening | 500 mm. Guidance for specification option: Maximum sash height 720 mm (unless otherwise specified). |
Dimensions | |
Overall depth | 830 mm. Bespoke. Guidance for specification option: Insert requirements. |
Overall width | 1200 mm. |
Lighting | |
Lighting type | LED lighting. |
Illuminance at work surface (minimum) | 800 lx. |
Services | |
Water | |
Sink unit | Not required. Required. |
Water supply | Not required. Cold water supply. Hot water supply. Reverse osmosis water supply. Demineralized water supply. |
Drainage | Manufacturer guidanceInsert requirements or omit. |
Electricity | |
Power requirements | 110 V, 50/60 Hz, single-phase. 220 V, 50/60 Hz, single-phase. Manufacturer guidanceA three-phase power supply can be ordered. Consult manufacturer for details. |
Electrical socket outlets | Four. Manufacturer guidanceSingle phase, 3A, 240 V, 50 Hz. |
Location | Sockets on front face of fume cupboard. |
Gas outlets | Not required. Nitrogen. |
Airflow indicator with audible and visual alarms | Constant airflow monitoring and display with visual alarm on screen and integrated internal red light alarm system. |
Controls | |
Controller type | Touch screen control panel, 7-inch. Guidance for specification option: Full-colour touch screen with air flow velocity display, low airflow alarms display, fan control on/off and calibration settings. |
Control modes | Eco mode, Night setback mode (pro only). |
Accessories | Not required. Centrifugal fans. Glove apertures. Multisash. Partitions. Shelves. Sumps. Vacuum tap. |
Worksurface | Polypropylene. Stainless steel. Ceramic. Epoxy. Trespa. |
Safety devices | Not required. Co2/powder fire supression. External interlock emergency stop. |
Contains Red List materials | No |
Country of material origin | Germany |
Material | Polypropylene |
Expected Life | Ten year |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
![]() | - | 1 |
![]() | - | 1 |