A single blade fire damper for HVAC ductwork.
Fire dampers are suitable for installation in arbitrary positions in vertical and horizontal passages of fire-separating constructions. The fire damper can be installed into:
Additional applications may be available, please reference product Technical Specifications for more detail.
A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors.
Features and benefits:
Color | Silver |
Finish | Galvanized |
Material | Steel Calcium silicate |
Shape | Rectangle Square |
Length | 375 mm |
Width | 180 mm 200 mm 225 mm 250 mm 280 mm |
Height | 180 mm 200 mm 225 mm 250 mm 280 mm |
Uniclass | |
CAWS | U90/443 Dampers, fire/ smoke |
Standard | |
Fire dampers | To EN 15650. |
Test | To EN 1366-2. |
Classification | To EN 13501-3. |
Aerodynamic performance | To EN 1751.Guidance for specification option: Damper body: Class C; Damper blade: Class 2. |
Arrangement | Single-blade. |
Classification | EIS90.EIS120.Manufacturer guidanceRefer to the manufacturer's literature for placement and installation details to achieve the required fire resistance values. |
Material | Zinc-coated steel. |
Fusible links | |
Fusing temperature | 72°C.Guidance for specification option: As standard. 104°C.147°C. |
Spare fusible links | Manufacturer guidanceInsert requirements or omit. |
Dimensions | Manufacturer guidanceConsult manufacturer's literature for performance details and insert requirements.
|
Duct connection | Mandik FFDM breakaway joint. Guidance for specification option: FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained. Refer to FFDM – Technical specifications for options and insert requirements. Breakaway joint (supplied by others). Guidance for specification option: Insert requirements. Manufacturer guidanceBreakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper. |
Material | Steel Calcium silicate |
Platform | Compatible | Version |
---|---|---|
- | 1 |
FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper
FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper
FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper
FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper
FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper
FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper
FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper
FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper