Verified by manufacturer 5 months ago
Two 24 V d.c. actuators
Natural casement roof single flap ventilator, suitable for natural smoke control and day-to-day ventilation.
Suitable for natural smoke control and provision of extract ventilation for most kinds of industrial and commercial buildings.
Particularly suited for installation into glazing systems.
Natural casement roof ventilator, suitable for natural smoke control and day-to-day ventilation.
Features and benefits:
Also available as a single flap ventilator with high aerodynamic, acoustic and thermal performance (Firelight FL3) or as a double flap ventilator (Firelight Duo); both specified separately.
Color | Silver Other |
Finish | Mill finish Powder-coated Anodized |
Material | Aluminium Polycarbonate Glass |
Shape | Rectangle Square |
Uniclass | |
CAWS | L10/47 Roof ventilators L10/490 Roof ventilators |
Product range |
Standard | To BS EN 12101-2.Guidance for specification option: CE marked. |
Opening type | B. |
Mounting | Roof mounted, onto curb.Roof mounted, onto glazing.Roof mounted, onto roof sheeting. |
Aerodynamic free area | Maximum overall ventilator size: 5 m².Manufacturer guidanceAerodynamic coefficient: up to 0.64. |
Reliability classification | Re 1000.Guidance for specification option: 10 000 cycles. |
Snow load classification | Up to 2000 N/m². |
Low ambient temperature classification | T (-15).Guidance for specification option: T(00) to T(-15). |
Wind load classification | Up to 2000 N/m². |
Resistance to heat classification | B300. |
Arrangement | Flap. |
Dimensions | |
Length | Manufacturer guidanceInsert requirements, throat length 700–2500 mm (in 1 mm increments), subject to maximum overall ventilator size limit: see Aerodynamic free area for maximum overall ventilator size. Consult manufacturer for details of overall size; the dimensions depend on the type of flap, the geometry of the ventilator and its opening angle. |
Width | Manufacturer guidanceInsert requirements, throat width 700–2500 mm (in 1 mm increments), subject to maximum overall ventilator size limit: see Aerodynamic free area for maximum overall ventilator size. Consult manufacturer for details of overall size; the dimensions depend on the type of flap, the geometry of the ventilator and its opening angle. |
Height | Manufacturer's standard. |
Controls | Two 24 V d.c. actuators, linear drives.Two 24 V d.c. actuator, chain drives.230 V a.c. electric tubular fail safe drives. |
Initiation | Local thermal fuse.Guidance for specification option: Opens the unit at a pre-selected temperature. External release signal.Guidance for specification option: Insert details. |
Materials | |
Ventilator | |
Frame | Corrosion-resistant 6063-T6 aluminium alloy.Guidance for specification option: Thermally broken. With stainless steel fixings. |
Glazing | Double-glazed, 32 mm thick.Guidance for specification option: Standard infill thickness. Double-glazed, custom thickness.Guidance for specification option: Insert requirements, 7–35 mm. Polycarbonate unit, 32 mm thick.Guidance for specification option: Standard infill thickness. Polycarbonate unit, custom thickness.Guidance for specification option: Insert requirements, 7–35 mm. Aluminium infill panel, insulated.Guidance for specification option: EN AW-6063 T6 aluminium alloy. Aluminium infill panel, uninsulated.Guidance for specification option: EN AW-6063 T6 aluminium alloy. |
Finish | Mill finish.Polyester powder-coated.Guidance for specification option: 70 µm thick as standard. Anodized.Guidance for specification option: 20 µm thick as standard. Other.Guidance for specification option: Special finishes available on request; consult manufacturer and insert requirements. |
Colour | Standard.Guidance for specification option: Mill finish/ anodized only. RAL.Guidance for specification option: Polyester powder-coated only; insert requirements. |
Seals | Double seals.Guidance for specification option: Used to reduce air leakage when closed. |
Resistance to fire | E. Guidance for specification option: To EN 13501-1. |
U-value | Up to 1.6 W/m²K. |
Air permeability | Class 3. Guidance for specification option: Maximum of 9 m³/h/m² or 2.25 m³/h/m at 100 Pa (to EN 12207:1999). |
Watertightness | Class 9A. Guidance for specification option: No leaks at static pressure of up to and including 600 Pa (to EN 12208:1999). |
Sound insulation | Up to 40 dB Rw. |
Locking | Manufacturer's standard. Guidance for specification option: For both electric and pneumatic versions, double-action locking mechanisms. For pneumatic version only, failsafe open. |