Verified by manufacturer 5 months ago
PL10 - Linear
BSI Kitemark
Certificate type
European Technical Approvals
Certificate type
A range of vacuum/ forced U-tube and linear heaters.
For industrial and commercial properties including warehouses, factories, showrooms, retail outlets, aircraft hangars, rail sheds, garage automotive workshops.
A range of vacuum (induced) / forced 9blown) U-tube and linear heaters that feature optimal comfort and energy savings, with two stage burner technology as standard. Two stage high/ low allows for fast warm up and recovery on high fire and maximum energy savings with steady state low fire.
Features and benefits:
Unitry gas fired radiant tube heating system consisting of individual SRP Powrmatic PVU/PVL/PU/PL/PVDL two stage Hi/Low fire vacuum burners. Each burner having automatic electronic sequence control box with three strike ignition, flame ionisation, control module error codes. – Airflow fault, – Flame – No call for heat, – Ignition Lockout, – Control Fault. and a multi functional gas governor block.
The SRP Powrmatic gas fired radiant heating system shall be manufactured to comply with ErP Lot20 seasonal efficiency. The system shall be installed in accordance with current IGE & IEE regulations and BS 6896.
The SRP Powrmatic PVU/PVL/PU/PL/PVDL radiant heating system shall operate under negative pressure or blown gas during operation with the inbuilt differential proving air pressure sensor in each of the burner housings sensing the correct amount of differential vacuum providing protection as dictated by BS EN777-4:1999.
Each radiant tube unit and set on completion in accordance with the manufacturers’ instructions.
Each burner shall be complete with gas isolation valve and flexible gas hose connection with union and installed as per manufacturers instruction manual.
The SRP Powrmatic single linier or twin parallel or double linier radiant emitter tube shall be Ø100mm mild steel tube, with none flake Calorised Aluminised finish. The Calorised tube shall be hot coated internally and externally with aluminium, then heat treated in a controlled furnace fusing the aluminium into the surface of the steel and ensuring that the seam weld is coated with aluminium.
A twist lock turbulator shall be employed where applicable within the assembled 100mm tube to maximise the tube heat transfer and swirl combustion gas improving its scrubbing action.
High Efficiency multi-faceted reflectors of low weight ASTM 1100 Aluminium shall direct radiant heat output downward and having a unique design profile to maximise the reflected radiant heat, End Caps to minimise convection loss, and galvanised suspension brackets for horizontal or angled mounting to maximise rigidity.
Through the roof or side wall proprietary flue system as appropriate with suitable rubberised roof flashing or wall terminal with plate.
------------------------------------------------------
Where applicable, the system shall be controlled from a Powrmatic single zone MC200v3 control incorporating optimum start and optimum stop, and a Radiant Black Bulb Sensor mounted at 1500mm AFFL.
----------------------------------------------------------
Where applicable, the system shall be controlled from a Powrmatic multi zone MC400 controller, controlling MC400 and up to four control temperature zones each having it own Radiant Black Bulb sensors mounted at 1500mm AFFL.
Color | Silver Black |
Material | Metal Manufacturer guidanceAluminium |
Shape | Rectangle |
Length | 3450 mm 5400 mm 6950 mm 9500 mm 9850 mm |
Width | 400 mm 900 mm |
Height | 250 mm 390 mm 400 mm |
Warranty description | One year Guidance for specification option: Labour. Two year Guidance for specification option: Parts. |
Uniclass | |
CAWS | T90/110 Heating system T90/110 Heating system |
Mounting | Ceiling. |
Length | 3450 mm. |
Arrangement | Horizontal.Angle mounted. |
Fuel | LPG.Natural gas. |
Controls | MC200 Energy saver controller. |
Flues and chimneys | 100 mm Flue. |
Accessories | None.Burner lockout indication.Sports guards.Side skirts. |
Integral accessories | Galvanized suspension brackets. |
Input | Natural gas: 8.5–11 kW; LPG: 8.5–10.5 kW. |
Contains Red List materials | No Manufacturer guidanceNone |
Country of material origin | Canada Manufacturer guidanceUK |
Country of product manufacture | United Kingdom Manufacturer guidanceCanada |
Recyclability | 95% |