NBS Source
I'm a manufacturer

Horizontal Fire Curtain - 120 min - HFC120E - Fire Curtain

Verified by manufacturer 21 days ago

Adexon Fire & Smoke Curtains Third party certifications:
  • Fire Safety Certification

    Certificate type

Horizontal fire curtain certified to 120 minutes integrity rating.

Jump to:
0151 422 9111 Website

Application

Suited to many different applications; some of the most common are:

  • Openings in floors, or ceilings.
  • Covering over and around.
  • Stopping fire spread between floors, for example, to separate levels of a building’s atria.

Description

The Adexon-HFC120E horizontal active fire curtain offers a fire protection solution for stopping the spread of fire between floors. Designed to limit and control the spread of fire for 120 minutes at over 1000°C. It achieves the rating of 120 minutes integrity (E).


Features and benefits:

  • The system is tested and certified to ISO/DIS 21524-1:2019.
  • The horizontal curtain features no visible supports, allowing for completely unobstructed atria and stairwells. This lets light flow and increases ventilation options in open plan spaces without extra structural supports.
  • Operation is via two 24 V d.c tubular motors (one motor to open, and one motor to close), controlled by an electronic control board and two small motor controller units.
  • Standard lead time is 10–12 weeks from approval of drawings.
  • Optional extras such as emergency retract buttons and obstruction warning are available upon request.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Steel

Fiber-glass

Polyurethane

Shape

Rectangle

Length

Bespoke

4610 mm

Guidance for specification option:

Maximum.

Width

Bespoke

3290 mm

Guidance for specification option:

Maximum.

Warranty description

Ten year

Uniclass

Pr_25_80_79_38 Horizontal active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Horizontal active fire curtain barriers

Standards

-

Barrier assemblies

To ISO 21524-1.

Test standards

To EN 1365-2:2014.

Third-party certification

Applus+ Certificate APF-1963.

Size

Guidance for specification option:

  • Maximum certified size: 3.29 x 4.61 m. Insert requirements or refer to a drawing.
  • Determine project requirements on a curtain-by-curtain basis through detailed design and scheduling. Refer to drawings for locations.

Performance

-

Fire resistance

RE 120.

Barrier units

Single.

Multiple.

Activation

Fire alarm signal.

Signal from local smoke or heat detector.

BMS.

Accessories

None.

Emergency retract buttons.

Obstruction warning.

Colour/ Finish

Galvanized.

Galvanized and powder-coated.

Guidance for specification option:

All standard and non-standard PPC colours are available. Insert requirements.

Sustainability data

Material

Steel

Fiber-glass

Polyurethane

Third party certifications

Fire Safety Certification

Fire Safety Certification

Adexon-HFC120E_60_90_120EW Horizontal Fire Curtain - Certificate APF-2136 - SPC-117 -- ISO DIS 21524-1 2019 -- Exp 25,06,30

Literature

Horizontal Fire Curtain Brochure HFC120E

Horizontal Fire Curtain Brochure HFC120E

HFC120E Drawing

HFC120E Drawing

HFC120E Uniclass Spec

HFC120E Uniclass Spec

Adexon Product Brochure

Adexon Product Brochure