NBS Source
I'm a manufacturer

In-line Thermal Disinfection Unit (ILTDU) - DWS Pathogen Control Device

Verified by manufacturer 1 month ago

Horne Engineering Ltd Third party certifications:
  • UK Water Regulation 4

    UK Water Regulation 4

    Certificate type

In-line thermal disinfection unit for tap or shower outlets.

Jump to:
BOS
+44 (0)1505 321455 Website

Application

The ILTDU, In-line Thermal Disinfection Unit, facilitates regular thermal disinfection of water system outlets (including downstream thermostatic showers, mixing valves or thermostatic taps) using available, system temperature, hot water supply.


For optimal DWS health and efficiencies, Horne recommends thermal disinfection be undertaken in conjunction with elevated velocity flushing of the upstream supply pipework to effectively remove and manage excess pipework biofilm.


Suitable for domestic water supplies of institutional environments, including healthcare, education, prison accommodation and sport and leisure facilities, to assist with protection against Pseudomonads, Legionellae and other waterborne pathogens.

Description

The In-Line Thermal Disinfection Unit (ILTDU) facilitates periodic high temperature thermal disinfection of water supply pipework using the readily available hot water supply.


Now the thermal regime can be extended to the point of water discharge: therefore, the wetted surfaces of all downstream components, including the TMV and the outlet fitting, can be raised to system temperature.


Required Accessory

General information

Color

Silver

Bronze

Finish

Metallic

Etched

Material

Brass

Stainless steel

Plastic

Polymer

Shape

Other

Length

147 mm

Width

53 mm

Height

89 mm

Warranty description

Uniclass

Pr_60_55_97_90 Thermal disinfection unitsPrimary

CAWS

S90/650 Flow-reducing/ servicing valves

Specification data - Thermal disinfection units

Certification

UK Water Reg 4.

Guidance for specification option:

Non-metallic materials in contact with potable water.

Accessories

Operation Key P/N 6236.

Guidance for specification option:

Required accessory.

Connections

Hot and cold, 15 mm compression.

Water pressure

Maximum working pressure (static): 10 bar.

Maximum temperature

85°C.

Materials

Brass alloy body, nitrile/PTFE seals, stainless steel four way link mechanism.

Guidance for specification option:

BS EN 12164 CW 617N.

Sustainability data

Country of product manufacture

United Kingdom

Material

Brass

Stainless steel

Plastic

Polymer

Recyclability

Can be recycled

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

UK Water Regulation 4

UK Water Regulation 4

Materials compliance - ILTDU

Literature

Horne In-Line Thermal Disinfection Unit (ILTDU)

Horne In-Line Thermal Disinfection Unit (ILTDU)

Instructions - Horne In-line Thermal Disinfection Unit (ILTDU)

Instructions - Horne In-line Thermal Disinfection Unit (ILTDU)

System proves effective in combatting P. Aeruginosa

System proves effective in combatting P. Aeruginosa

CPD: Engineering versus Pseudomonas...and retrograde contamination of domestic water services

CPD: Engineering versus Pseudomonas...and retrograde contamination of domestic water services

Case studies

Revolutionising healthcare water hygiene: proven, effective, and sustainable

Revolutionising healthcare water hygiene: proven, effective, and sustainable