Verified by manufacturer 24 days ago
KAMOUFLAGE MP 1V120 smoke control damper
DoP
Certificate type
UK Conformity Assessed (UKCA)
Certificate type
Classification report acc. to EN 13501-4
Certificate type
Automatic (AOV) Rectangular EIS smoke control damper (SCD) - fire resistance up to 120 minutes. Can be easily integrated in many smoke control systems thanks to its aesthetic finishing possibilities.
KAMOUFLAGE MP - Automatic Smoke Control Damper (AOV) - 60-90-120 minutes for aesthetic, architectural designs
Automatic (AOV) Rectangular EIS smoke control damper (SCD) - fire resistance up to 120 minutes.
Highest classification: EI 120 (ved i o) S 1500 C10000 AA multi
Can be easily integrated in many smoke control systems thanks to its aesthetic finishing possibilities.
Kamouflage MP Certified installations and sealing methods
Kamouflage MP Fields of application
Kamouflage MP Building applications:
The Kamouflage MP is the ideal smoke control damper to use in buildings where an aesthetic look is a must, as the product comes with many different aesthetical finishes.
Relevant Links:
KAMOUFLAGE MP - Automatic Smoke Control Damper (AOV) - 60-90-120 minutes for aesthetic, architectural designs
Automatic (AOV) Rectangular EIS smoke control damper (SCD) - fire resistance up to 120 minutes.
Highest classification: EI 120 (ved i o) S 1500 C10000 AA multi.
Can be easily integrated in many smoke control systems thanks to its aesthetic finishing possibilities.
Kamouflage MP product features:
Kamouflage MP Installer & User benefits:
Kamouflage MP Range: (Width/Height)
Notes:
Relevant Links:
Color | White Other Beige Black Blue |
Finish | Natural |
Material | Aluminium |
Shape | Rectangle |
Length | 250 mm Guidance for specification option: Depth. |
Width | 350 mm 400 mm 450 mm 500 mm 550 mm Manufacturer guidanceNominal. |
Height | 385 mm 415 mm 445 mm 475 mm 505 mm Manufacturer guidanceNominal. |
Warranty description | One year |
Uniclass | |
CAWS | U90/445 Dampers, smoke |
Standard | To EN 12101-8:2011. |
Classification | |
Standard | To EN 13501-4. |
Multi-compartment | |
Integrity class | EI 90.Guidance for specification option: Minimum. EI 120.Guidance for specification option: Consult manufacturer for installation requirements on how to achieve classification. |
Suitability | Ve duct. |
Smoke leakage | S. |
Under pressures | 1500. |
Inside or outside | (i ↔ o). |
Smoke control use | C10000. |
Activation | AA – automatic. |
Actuators | Motorized - drive open & close, 24 V d.c.Guidance for specification option: -10/ +15%. Motorized - drive open & close, 48 V d.c.Guidance for specification option: -10/ +15%. Not required (manual).Guidance for specification option: Key provided. |
Dimensions | Guidance for specification option: Consult manufacturer's literature for performance details and insert requirements:
Overall height = nominal height + 54 mm. Overall width = nominal width + 54 mm. Consult manufacturer unit weights based on requirements (10.1–31.7 kg). |
Accessories | VD24 - natural magnet 24 V DC. EASY-KAP ME/MP - mounting frame. EASY-KGC ME/MP 1V - mounting frame with hinged drop guard grid. TL - trailing lead 3 m for external connection. FDCU - Limit switch (open/closed). |
Third-party certification | CE marked 1812 Efectis_requested. |