NBS Source
I'm a manufacturer
Compare variants

LINETRAXX® PEM353 Power Quality Measuring - Universal Measuring Device

Verified by manufacturer 5 days ago

PEM353-N

Bender UK Variant:
Third party certifications:
  • CE Marking

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

A digital universal measuring device for electricity supply networks.

Jump to:
+44 (0) 1229 480123 Website

Application

  • Modern indicating instrument for electrical quantities, e.g. as a replacement for analogue indicating instruments.
  • Power quality monitoring.
  • Limit value monitoring (setpoints) with alarm forwarding.
  • Measurement and monitoring of the N conductor.
  • Energy and power measurement, e.g. as part of energy data monitoring.

Description

The digital universal measuring device PEM353 is used to record and display measured quantities of an electricity supply network, and make them available via the communication interface.

The range of measurements extends from voltages and currents to power and energy meters to measured quantities of the voltage quality, such as THD and the individual harmonics up to the 31st order.

The PEM353 is suitable for use in 2-, 3- and 4-wire systems and in their respective versions as TN, TT and IT systems. This allows monitoring single and polyphase systems. With its standardised dimensions of 96 x 96 mm, the device is intended for front panel mounting.

Features and benefits:

  • Numerous measured quantities (see manufacturer's literature for features/functions).
  • Power quality monitoring.
  • Limit value monitoring (setpoints) with alarm forwarding.
  • Energy and power measurement with storage and time of use.
  • Configurable start page with four measured quantities.
  • N conductor measurement and monitoring (PEM353-N only).

General information

Color

Yellow

Shape

Square

Length

96 mm

Width

80 mm

Height

96 mm

Warranty description

Two year

Uniclass

Pr_80_51_51_22 Digital metering equipmentPrimary
Pr_80_51_51_23 Digital multifunction metering equipment

CAWS

V90/430 Electrical accessories

Specification data - Digital metering equipment

Standards

To DIN EN 62053-22, DIN EN 61557-12 and DIN IEC 61554.

Display

LCD graphic display.

Rated voltage

TN and TT system (earthed): a.c. 230/400–400/690 V, CAT III 600 V IT system (unearthed): a.c. 400–480 V, CAT III 300 V/ a.c. 500–690 V, CAT II 1000 V.

Phase arrangement

Single phase, two-wire.

Three phase, three-wire.

Three phase, four-wire.

Current measuring range

Via external CTs 1 A or 5 A.

Rated frequency

45–65 Hz.

Metering functions

Phase (V).
Line-to-line voltages (V).
Phase currents (A).
Neutral current (A).
Residual current (A).
Frequency (Hz).
Power per phase conductor (kVA).
Displacement factor cos φ.
Power factor (λ).
Active and reactive energy import (kWh, kvarh).
Voltage phase angle (°).
Current phase angle (°).
Voltage unbalance (%).
Current unbalance (%).
Harmonic distortion (THD, TOHD, TEHD) for U and I.
k-factor for I.
Crest factor for I.
Total demand distortion (TDD) for I.

Mounting

Front panel.

Ingress protection (minimum)

IP20 (installation); IP54 (front, with rubber seal).

Outputs

2 x relay.

Communications

RS-485 (Modbus RTU, BACnet MS/TP, DNP).

Connections

Screw-type terminals, plug-in connector.

Input current

Current inputs (I1, I2, I3): 5 A/ 1 A.
Current inputs (I4): 5 A.

Sustainability data

Country of product manufacture

Germany

Recyclability

Can be returned to manufacturer for recycling under WEEE regulations

Third party certifications

CE Marking

CE Marking

EU - Declaration of Conformity PEM35x

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

UKCA PEM35x

Literature

PEM353 Data Sheet

PEM353 Data Sheet

Power Quality Flyer

Power Quality Flyer

PEM353 Quickstart Guide

PEM353 Quickstart Guide

Product overview Power quality and energy measurement

Product overview Power quality and energy measurement

PEM353 Manual

PEM353 Manual