Radiation shielding X-ray operator screen. Raybloc's frameless operator screens are the hygienic and modern solution to an X-ray screen, designed with the radiographer in mind.

Jump to:
BOS
+4401902 633383 Website

Application

Suitable for industries such as hospitals, dental surgeries and veterinary practices.

Description

A solution for shielding against harmful radiation while maintaining exceptional clarity and functionality. Providing fully bespoke fixed operator X-ray screens that are manufactured to the latest NHS HTM and infection control standards, the X-ray screens are made to the highest quality of safety and standard in the industry.


The X-ray screens can be designed to match existing decoration to precise dimensions and are manufactured to the highest quality available from renewable sustainable materials. They have a unique rounded U-shaped barrier channel, providing a bash-resistant, soft touch edge which prevents sharp chips from wear and tear over time.


Available in any colour laminate finish with a satin anodized smooth soft touch frame to ensure they fit perfectly within their surroundings. They are fully bespoke screens made to fit project requirements. The frameless design offers a sleek and unobtrusive appearance. The absence of a traditional frame allows for uninterrupted visibility, ensuring operators have a clear line of sight while performing critical tasks. This enhances precision and efficiency, promoting a seamless workflow in medical departments and other radiation-intensive environments.


Wherever radiation protection is critical, the screen offers peace of mind, optimal safety and a seamless protected workspace. The Raybloc Radiation Protective Frameless Operator Screen features state-of-the-art lead glass that provides superior radiation attenuation properties, effectively blocking X-ray radiation, and safeguarding operators and personnel from potential health risks associated with prolonged exposure.


Features and benefits:

  • Bespoke size options to fit project needs.
  • Lead equivalence is available for 2.24 mmPb (Code 5) to 2.65 mmPb (Code 6).
  • Optional worktop and shelves.
  • 10-year material and workmanship warranty.
  • All timber products purchased and used by Raybloc (X-ray Protection) Ltd are FSC-certified for sustainability.
  • Manufactured in the United Kingdom.
  • All timber products purchased and used by Raybloc (X-ray Protection) Ltd are FSC certified.
  • Available with Sense-X® LED mood lighting (see Raybloc page for more).

General information

Color

Beige

Black

Blue

Brown

Cream

Show more

Manufacturer guidance

Any colour available.

Finish

Laminated

Material

Medium density fibreboard (MDF)

Lead

PVC

Laminate

Glass

Show more

Shape

Rectangle

Other

Square

Length

Bespoke

Width

49 mm

Height

Bespoke

Guidance for specification option:

2000mm standard. 2400 mm maximum.

Manufacturer guidance

2000mm

Warranty description

Ten year

Uniclass

Pr_40_70_51_99 X-ray radiation screensPrimary

CAWS

L10/560 Glazed screen system

N10/110 Purpose-made

N10/10 Purpose-made

Specification data - X-ray radiation screens

Certification

FSC certified.

Accessories

Not required.

Worktop.

Guidance for specification option:

38 mm post-formed – white laminate.

Shelf/Plinth.

Guidance for specification option:

28 mm post-formed – white laminate.

Features:

  • Frameless top glass edge.
  • Conforms to HTM infection control standards.
  • Hidden fixing detail - no visible screws.

Components

Two panels.

Material

46 mm MDF moisture-resistant core – lead-lined.

Guidance for specification option:

  • Length: As required to achieve total length (maximum width 1600 mm per panel before panels are joined together - minimum width of 150 mm).
  • Connection joints: Male and female edges – lead-lined.

Finish

Laminate.

Laminate – custom vinyl graphic.

Screen height

Manufacturer's standard.

Manufacturer guidance

  • Bottom Panel: Standard 1000 mm | As required.
  • Top Panel/Glazing: Standard 1000 mm | As required (maximum 1400 mm).
  • Total Height: Standard 2000 mm | As required (maximum 2400 mm).

Size:

-

Manufacturer guidance

Consult manufacturer and insert requirements.


Length:

As required to achieve total length (maximum width of 1600 mm per panel before panels are joined together - minimum width of 150 mm).

Fixing

Fixed to the wall.

Guidance for specification option:

100 mm solid top panel required.

Edges

PVC edge banded.

Frame

White powder-coated aluminium extrusions – lead-lined.

Guidance for specification option:

Insert size and angle requirements:

  • Standard Profile: 35–60 x 49 mm (maximum length of 2400 mm).
  • Angle: 90, 120, 135, 150 or 180°.

Glazing

Med-X radiation protective glass – bevelled and polished upper exposed edge.

RD50 radiation protective glass – bevelled and polished upper exposed edge.

Manufacturer guidance

  • Glazing Seal: Neoprene – no dirt traps.
  • Glass Thickness: Code 5, 2.24 mm Pb – 7.5-9 mm, Code 6, 2.65 mm Pb – 9-10.5 mm.
  • Size: As required to suit the requested screen size (maximum sheet size of 2000 x 1200 mm).

Sustainability data

Contains Red List materials

Yes

Manufacturer guidance

Lead

Country of product manufacture

United Kingdom

Material

Medium density fibreboard (MDF)

Lead

PVC

Laminate

Glass

Show more

Third party certifications

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

ISO 14001 Environmental Management Systems

ISO 14001 Environmental Management Systems

CERTIFICATE OF REGISTRATION

ISO 9001 Quality Management

ISO 9001 Quality Management

ISO 9001:2015

Literature

Fujifilm Bedford | A Photographic Study

Fujifilm Bedford | A Photographic Study

Raybloc Radiation Protective Frameless Operator Screen Leaflet

Raybloc Radiation Protective Frameless Operator Screen Leaflet

Raybloc Radiation Protective Free Standing Frameless Operator Screen - Specification

Raybloc Radiation Protective Free Standing Frameless Operator Screen - Specification

Case studies

Bronglais Hospital Aberystwyth

Bronglais Hospital Aberystwyth

Singleton Hospital Swansea

Singleton Hospital Swansea

Birmingham Heartlands Hospital

Birmingham Heartlands Hospital