NBS Source
I'm a manufacturer

Roda Louvre Window - AOV Smoke vent SHEV - Louvre

Verified by manufacturer 24 days ago

Lamilux Rooflights Ltd Third party certifications:
  • TUV - Safety and Quality Report

    Certificate type

Thermally separated aluminium framed louvre windows for natural ventilation or smoke and heat extraction.

Jump to:
01284 749051 Website

Application

Suitable for installation in vertical commercial facades.

Description

The TGL ISO is the thermally separated version of the NTL. Window and slat frames are made of thermally separated aluminium profiles with a frame construction depth of 50, 60 or 70 mm. The TGL ISO is approved as a natural smoke and heat extracting system to EN 12101-2.


Features and benefits:

  • Function at low temperatures: T-20, subject to model and size.

Seals:

  • Lateral with sealing brushes, horizontal profile joints with sealing brushes and EPDM gasket.

General information

Color

Clear

Finish

Glazed

Material

Aluminium

Glass

Shape

Rectangle

Square

Length

800 mm

1000 mm

1200 mm

Width

1200 mm

1500 mm

1800 mm

2000 mm

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary
Pr_30_59_98_02 Aluminium window units

CAWS

L10/54 Louvres

L10/490 Roof ventilators

L10/47 Roof ventilators

L10/650 Metal louvres

Product range

Smoke ventilation

Specification data - Natural smoke and heat exhaust ventilators

Standard

To EN 12101-2.

Aerodynamic free area

S200 -S1: 800 x 2000 mm (Aa 0.77 m², Ageo 1.1 m²).

Guidance for specification option:

11 louvre.

S200 -S2: 1000 x 1500 mm (Aa 0.72 m², Ageo 1.05 m²).

Guidance for specification option:

Eight louvre.

S200 -S3: 1000 x 2000 mm (Aa 0.98 m², Ageo 1.41 m²).

Guidance for specification option:

11 louvre.

S200 -S4: 1200 x 1200 mm (Aa 0.73 m², Ageo 0.98 m²).

Guidance for specification option:

Seven louvre.

S200 -S5: 1200 x 1800 mm (Aa 1.07 m², Ageo 1.53 m²).

Guidance for specification option:

Ten louvre.

Wind load classification

To EN 12101-2:2003, WL 3000.

Materials

-

Ventilator

-

Frame

Extruded aluminium.

Guidance for specification option:

 Profiles with a frame construction depth of 50 mm and a frame face width of 38 mm.

Louvres

Aluminium panel louvre blades.

Guidance for specification option:

Non-thermally broken, extruded aluminium panel louvre blades.


  • Total thickness of slats: BT50 - 24 mm, BT60 - 32 mm, BT70 - 44 mm.
  • BT50 variable slat height: 120–400 mm.
  • BT60 / BT70 variable slat height: 200–400 mm.


Finish

Anodized.

Guidance for specification option:

25 micrometres.

Powder coated.

Guidance for specification option:

60–80 micrometres.

Colour

Anodized silver - E6 EV1.

Anodized E6/C31 - 35.

Guidance for specification option:

Insert requirements.

RAL.

Guidance for specification option:

Can be powder coated to any RAL colour. Insert requirements. 

Seals

Lateral with sealing brushes, horizontal profile joints with sealing brushes and EPDM gasket.

Fire resistance

To EN 12101-2:2003, Resistance to heat B 300 E.

Acoustic performance rating

To DIN EN ISO 717-1, 38 dB.

To DIN EN ISO 717-1, 39 dB.

Standard:

To EN 14351-1:2006+A1:2010. Resistance to repeated opening and closing class 3 (DIN EN 1191).

Operation

Electrically via 230 V AC.

Electrically via 24 V DC.

Pneumatically.

Electrical supply

E-motor WAL, 24V, 0,65 A, 1600 N, IP50, E6/EV1, stroke 36 mm with 3,0 m cable (black), without pushbutton, without control.

Fixing

Profiles for fixing in post beam construction, window construction or masonry.

Dimensions and configurations

Insert requirements.

Guidance for specification option:

  • Minimum frame width = 300 mm.
  • Maximum frame width = 2000 mm (broader elements are available divided by glazing bars).
  • Maximum frame width can be extended to 2500 mm with tandem control or double-acting drive.


Sustainability data

Contains Red List materials

No

Country of product manufacture

Germany

Material

Aluminium

Glass

Third party certifications

TUV - Safety and Quality Report

TUV - Safety and Quality Report

ISO 50001:2011

TUV - Safety and Quality Report

TUV - Safety and Quality Report

ISO 9001 : 2015

Literature

roda Louvre Window_datasheet

roda Louvre Window_datasheet

LAMILUX Roofs of Light Brochure

LAMILUX Roofs of Light Brochure