S-Line® Pillows

Verified by manufacturer 19 days ago

S100FP – S-Line® Sausage

FSi Limited Variant:
Third party certifications:
  • UL-EU Certified

    UL-EU Certified

    Certificate type

Fire resistant penetration sealing system.

Jump to:
+44 (0)1530 515130 Website

Application

Application / Use:

  • To reinstate fire resistance through rigid walls and floors.
  • Multi-service penetrations.
  • Prevention of air leakage.
  • Maintains Acoustic performance.
  • Assumed working life 30 years.
  • Fire Stopping within steel cable trunking · For internal use.

Description

S-Line Fire Pillow are a fire resistant penetration sealing

system used to create a temporary or permanent fire barrier

around single or multi-service penetrations to prevent the

passage of fire through a compartment wall or floor,

especially suitable where services are continuously being

changed or replaced.

General information

Color

Grey

Material

Glass Fibre

Intumescent

Fabric

Guidance for specification option:

Cloth.

Shape

Rectangle

Uniclass

Pr_25_80_81_43 Intumescent pillowsPrimary

CAWS

P12/345 Intumescent pillows

Product range

Others

Specification data - Intumescent pillows

Composition

Glass cloth bag with organic fillers and intumescent additives.

Size

330 x 50 x 20 mm.

Fire performance

To BS EN 1366-3:2009, BS 476 : Parts 20 and 22 and BS EN 13501-2:2016.

Guidance for specification option:

See UL-EU-00640-CPR for fire resistance performance.

For BS 476: Parts 20 and 22, contact technical.fsi.uk@etexgroup.com for details.

Sound insulation rating

To EN 10140, 43 dB.

Air leakage

To EN 1026, 600 Pa.

Guidance for specification option:

Contact technical.fsi.uk@etexgroup.com for details.

Third-party certification

CE Mark ETA-20/1031, UL-EU-00640-CPR; ISO 9001: 11378.

Weight

50g.

Walls

-

Manufacturer guidance

The installer must ensure that all services are within the scope of application for S-Line Pillows as outlined

in UL-EU-00640-CPR. Install the S-Line Fire Pillows in such a way that all joints are staggered in each layer

until you have filled all gaps within the wall or floor.


Walls - S-Line Pillows must be installed centrally within the fire line so as they overlap both sides of the

wall.

Floor surface

-

Manufacturer guidance

The installer must ensure that all services are within the scope of application for S-Line Pillows as outlined

in UL-EU-00640-CPR. Install the S-Line Fire Pillows in such a way that all joints are staggered in each layer

until you have filled all gaps within the wall or floor.


Steel mesh (50 mm square with 5 mm wire) is mechanically fixed with suitable non-combustible fixings to the soffit of the floor or within the reveal of the aperture via vertical returns at the edges of the mesh. The S Line pillows are tightly packed into the opening and around the services.

Sustainability data

Country of product manufacture

United Kingdom

Material

Glass Fibre

Intumescent

Fabric

Guidance for specification option:

Cloth.

Manufacturing plant location

Third party certifications

UL-EU Certified

UL-EU Certified

UL-EU-00640-EN - S-Line Pillows