Verified by manufacturer 24 days ago
1200 x 1500 mm - Solo motor
Passive House Institute - Certificate
Certificate type
EPD
Certificate type
TUV - Safety and Quality Report
Certificate type
Passivhaus-certified smoke and ventilation glass rooflight.
Suitable for residential and commercial new buildings and renovations looking to achieve Passivhaus certification.
Roof types: Flat roofs, and roofs up to a 10° pitch.
Passivhaus-certified smoke ventilation glass rooflight / Skylight.
Includes all the features of the standard Glass Skylight FE Passivhaus, but with the added safety features of an EN 12101-2 certified electrical smoke and heat exhaust ventilator rooflight.
Features and benefits:
Color | Other |
Finish | Powder-coated Mill |
Material | Glass Aluminium Glass Reinforced Plastic (GRP) Polyurethane |
Shape | Square Rectangle |
Length | 1000 mm 1200 mm 1500 mm |
Width | 1000 mm 1200 mm 1500 mm |
Uniclass | |
CAWS | L10/490 Roof ventilators L10/460 Rooflights L10/45 Rooflights |
Standard | To BS EN 12101-2. |
Third-party certification | Passivhaus-certified.Guidance for specification option: Efficiency class: C. |
Mounting | Roof-mounted. |
Aerodynamic free area | 1.12 m². |
Reliability classification | Re 1000. |
Snow load classification | SL 1387. |
Low ambient temperature classification | T (-15).Guidance for specification option: Operating temperature: -15°C to +75°C. |
Wind load classification | WL 1500.Guidance for specification option: Class C5, to EN 12211. |
Arrangement | Glazed. |
Dimensions | |
Length | 1500 mm. |
Width | 1200 mm.Guidance for specification option: Hinged on the short side. |
Controls | Not required.SHEV control system.Guidance for specification option: Required to operate the ventilation function. |
Initiation | Automatic. |
Materials | |
Ventilator | |
Frame | Aluminium, with polyurethane (PU) foam core. |
Glazing | Quadruple toughened and laminated glass, clear.Guidance for specification option: Light transmission: 66%. Energy transmittance: 0.49. Quadruple toughened and laminated glass, 60/30 solar control coating.Guidance for specification option: Light transmission: 50%. Energy transmittance: 0.28. Quadruple toughened and laminated glass, 50/25 solar control coating.Guidance for specification option: Light transmission: 41%. Energy transmittance: 0.23. Quadruple toughened and laminated glass, 70/37 solar control coating.Guidance for specification option: Light transmission: 57%. Energy transmittance: 0.32. Bespoke.Guidance for specification option: Consult manufacturer and insert requirements. Manufacturer guidanceCWCT class 2 non-fragile.
|
Finish | Principal components polyester powder-coated. |
Colour | Manufacturer guidanceInsert RAL colour requirement. Dual powder coating is available if different internal and external finishes are preferred. |
Integral upstands | |
Material | GRP, insulated - 500 mm.Guidance for specification option: Suitable for roofs from 6° up to 10° pitch. GRP, insulated - 500 mm with 5° inclination.Guidance for specification option: Suitable for roofs from 0° up to 5° pitch. |
Finish | Powder coating. |
Colour | White, RAL 9016. |
Seals | Triple step sealing system. |
Accessories | Not required.Control panel.Guidance for specification option: Must be compliant with EN 12101 parts 9 & 10. Wind and rain detectors. |
Unit weight | 174–182 kg. Manufacturer guidanceDependent on upstand. |
Operating voltage | 1 x 24 V (7.5 A). Guidance for specification option: Minimum 8 A control panel required. |
Motor | Solo motor - Mill finish. Guidance for specification option: As standard. Solo motor - RAL, colour. Guidance for specification option: Powder coating to a standard RAL colour upon request. Manufacturer guidanceOpens to 165° in under 60. |
Air permeability | To BS EN 1026, Class 4. |
Watertightness | To BS EN 12208, Class 4. |
Material | Glass Aluminium Glass Reinforced Plastic (GRP) Polyurethane |