NBS Source
I'm a manufacturer
Compare variants

vTherm°e Heat Interface Unit - Electronically Controlled HIU

Verified by manufacturer 9 months ago

vTherm°e with insulated valve rail

Vital Energi Ltd Variant:
Third party certifications:
  • QA Certificate

    QA Certificate

    Certificate type

Electronically controlled heat interface unit.

Jump to:
BOS
+44 (0)1254 296 000 Website

Application

For domestic applications on heat networks or communal heating systems.

Description

Electronically controlled twin plate hydraulic heat interface unit (HIU), designed to provide instantaneous hot water and heating to the dwelling.


Features and benefits:

  • Domestic hot water (DHW) output up to 60 kW.
  • Heating (HTG) output up to 10 kW.
  • DHW and HTG controlled by pressure independent control valves (PICVs).
  • Fully insulated expanded polypropylene (EPP) casing.
  • Innovative cooling area to reduce ambient temperatures to extend component life.
  • Heat meter and pressure gauge visible with casing installed.
  • Insulated case constructed in three sections to improve access for maintenance and commissioning.
  • Standing heat loss of: 60 or 70°C: 31 W.
  • vTherm°e achieved the lowest Volume-Weighted Average Return Temperatures (VWART) at a primary flow temperature of 60°C of any BESA tested HIU: 70°C: 27.9°C (VWART). 60°C: 29°C (VWART).
  • In periods with no DHW or heating demand, the HIUs standing heat loss shall be a maximum of 32 W.
  • WRAS approved.

Material:

  • Pipes, fittings, valves (primary and heating): 1.4301 (AISI 304), CW617N, CW614N, CW602N, CW625N, GG15.
  • Pipes, fittings, valves (domestic hot water): 1.4404 (AISI 316L), CW617N, CW617N, CW602N.
  • Heat exchanger: 1.4404 (AISI 316L) Cu Brazing.
  • Insulation: Expanded polypropylene (EPP).

Some additional materials are used by component manufacturers such as valves and pumps. These are in small components within the assembly.

General information

Color

Black

Grey

Finish

Matt

Textured

Material

Polypropylene

Guidance for specification option:

Casing.

Shape

Rectangle

Length

690 mm

Width

530 mm

Height

250 mm

Warranty description

One year

Guidance for specification option:

One year from date of commissioning on replacement parts only.

Uniclass

Pr_60_60_38_36 Heat interface unitsPrimary

CAWS

T90/110 Heating system

T90/110 Heating system

Specification data - Heat interface units

Duty

-

Primary flow temperature

60–90°C.

Primary return temperature

70°C Primary Flow = 27.9°C; 60°C Primary Flow = 29°C (Volume-Weighted Average Return Temperatures (VWART)).

Pressure drop

<50 kPa (primary side), <10 kPa (heating).

Flow rate

0.32 L/s.

Heating supply temperature

Maximum 80°C.

Hot water supply temperature

Maximum 60°C.

Casing

Fully insulated EPP casing.

Insulation

Expanded polypropylene.

Components

-

Primary

Manufacturer's standard.

Secondary

Manufacturer's standard.

Controls

Electronically controlled. The HIU controller shall utilize the secondary side DHW and heating temperatures to control Pressure Independent Control Valves (PICVs) located on the primary side of both plate heat exchangers to maintain the temperature. A keep warm function maintains a primary flow temperature at the unit.

Integral accessories

Insulated valve rail.

Guidance for specification option:

Helps minimize losses.

Standard

CE, BESA, WRAS.

Overall sound power level

31.8 dB.

Weight

30 kg (dry), 35 kg (wet).

Electrical requirements

230 V, 5 A (50 Hz).

Guidance for specification option:

Maximum power consumption: 60 W.

Accessories/ Other requirements

None.

Apartment weather compensation.

Bluetooth.

Flushing bypass assembly.

Intelligent data collection.

Show more

Colour

Black.

Grey.

Finish

Matt

Textured

Hot water system (HWS) capacity (minimum)

60 kW.

HeatingCapacity

10 kW.

HWS temperature

55°C.

Heating secondary flow temperature (UFH)

45°C.

Heating secondary return temperature (UFH)

35°C.

Heating secondary flow temperature (Radiators)

60°C.

Heating secondary return temperature (Radiators)

40°C.

HIU primary pressure rating

10 bar.

Guidance for specification option:

Standard.

16 bar.

Guidance for specification option:

On request.

Maximum HIU primary differential pressure

4 bar.

Maximum secondary heating working pressure:

2.5 bar.

Secondary heating safety relief valve pressure

3 bar.

Maximum secondary main cold water (MCW)/ domestic hot water (DHW) pressure

10 bar.

Minimum MCW pressure

1 bar.

Sustainability data

Contains Red List materials

Yes

Guidance for specification option:

Contains PVC in some cables.

Country of material origin

-

Manufacturer guidance

Several European countries including Denmark, Germany and Switzerland.

Country of product manufacture

United Kingdom

Recyclability

90%+ of weight

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

90 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Third party certifications

QA Certificate

QA Certificate

WRAS: Approved

Literature

vTherm°e (Electronic) Datasheet

vTherm°e (Electronic) Datasheet

vTherm°e (Electronic) Installation Commissioning and Maintenance Manual

vTherm°e (Electronic) Installation Commissioning and Maintenance Manual