Verified by manufacturer 9 months ago
vTherm°e with insulated valve rail
QA Certificate
Certificate type
Electronically controlled heat interface unit.
For domestic applications on heat networks or communal heating systems.
Electronically controlled twin plate hydraulic heat interface unit (HIU), designed to provide instantaneous hot water and heating to the dwelling.
Features and benefits:
Material:
Some additional materials are used by component manufacturers such as valves and pumps. These are in small components within the assembly.
Color | Black Grey |
Finish | Matt Textured |
Material | Polypropylene Guidance for specification option: Casing. |
Shape | Rectangle |
Length | 690 mm |
Width | 530 mm |
Height | 250 mm |
Warranty description | One year Guidance for specification option: One year from date of commissioning on replacement parts only. |
Uniclass | |
CAWS | T90/110 Heating system T90/110 Heating system |
Duty | |
Primary flow temperature | 60–90°C. |
Primary return temperature | 70°C Primary Flow = 27.9°C; 60°C Primary Flow = 29°C (Volume-Weighted Average Return Temperatures (VWART)). |
Pressure drop | <50 kPa (primary side), <10 kPa (heating). |
Flow rate | 0.32 L/s. |
Heating supply temperature | Maximum 80°C. |
Hot water supply temperature | Maximum 60°C. |
Casing | Fully insulated EPP casing. |
Insulation | Expanded polypropylene. |
Components | |
Primary | Manufacturer's standard. |
Secondary | Manufacturer's standard. |
Controls | Electronically controlled. The HIU controller shall utilize the secondary side DHW and heating temperatures to control Pressure Independent Control Valves (PICVs) located on the primary side of both plate heat exchangers to maintain the temperature. A keep warm function maintains a primary flow temperature at the unit. |
Integral accessories | Insulated valve rail. Guidance for specification option: Helps minimize losses. |
Standard | CE, BESA, WRAS. |
Overall sound power level | 31.8 dB. |
Weight | 30 kg (dry), 35 kg (wet). |
Electrical requirements | 230 V, 5 A (50 Hz). Guidance for specification option: Maximum power consumption: 60 W. |
Accessories/ Other requirements | None. Apartment weather compensation. Bluetooth. Flushing bypass assembly. Intelligent data collection. |
Colour | Black. Grey. |
Finish | Matt Textured |
Hot water system (HWS) capacity (minimum) | 60 kW. |
HeatingCapacity | 10 kW. |
HWS temperature | 55°C. |
Heating secondary flow temperature (UFH) | 45°C. |
Heating secondary return temperature (UFH) | 35°C. |
Heating secondary flow temperature (Radiators) | 60°C. |
Heating secondary return temperature (Radiators) | 40°C. |
HIU primary pressure rating | 10 bar. Guidance for specification option: Standard. 16 bar. Guidance for specification option: On request. |
Maximum HIU primary differential pressure | 4 bar. |
Maximum secondary heating working pressure: | 2.5 bar. |
Secondary heating safety relief valve pressure | 3 bar. |
Maximum secondary main cold water (MCW)/ domestic hot water (DHW) pressure | 10 bar. |
Minimum MCW pressure | 1 bar. |
Contains Red List materials | Yes Guidance for specification option: Contains PVC in some cables. |
Country of material origin | Manufacturer guidanceSeveral European countries including Denmark, Germany and Switzerland. |
Country of product manufacture | United Kingdom |
Recyclability | 90%+ of weight |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 90 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |