Design .11 - Manual control and thermal with terminal switch

Mandik UK Limited Variant:
Third party certifications:
  • DoP

    DoP

    Certificate type

  • Certificate of constancy of performance

    Certificate type

  • EPD

    EPD

    Certificate type

A manual or motorised fire damper for air conditioning ducts.

Jump to:
0117 4526376 Website

Application

The fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions. The fire damper can be installed into:

  • Solid wall construction with a minimum thickness of 150 mm.
  • Solid ceiling construction with a minimum thickness of 150 mm.

Additional applications may be available, please reference product Technical Specifications for more detail.

Description

A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors.

Features and benefits:

  • Dampers from ø 200 to ø 800 mm.
  • CE certified to EN 15650.
  • Tested in accordance with EN 1366-2.
  • Classified to EN 13501-3+A1.
  • Fire resistance EI 180 S - 500 Pa.
  • Damper actuating: mechanical or electrical.

General information

Color

Silver

Finish

Galvanized

Material

Steel

Calcium silicate

Shape

Circle

Length

300 mm

500 mm

Width

200 mm

225 mm

250 mm

280 mm

300 mm

Show more

Height

200 mm

225 mm

250 mm

280 mm

300 mm

Show more

Warranty description

One year

Two year

Manufacturer guidance

  • The manufacturer provides a warranty of 24 months from the date of dispatch for the dampers.
  • In case of using a Schischek actuator, the manufacturer provides a 12-month warranty for the actuator from the date of shipment.

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To EN 15650.

Test

To EN 1366-2.

Classification

To EN 13501-3.

Aerodynamic performance

To BS 1751.

Guidance for specification option:

Damper body: Class C; Damper blade: Class 3.

Arrangement

Single-blade.

Classification

EIS180.

Manufacturer guidance

Refer to the manufacturer's literature for placement and installation details to achieve the fire resistance value.

Material

Zinc-coated steel.

Accessories

Limit switch signalling the damper blade position "CLOSED".

Fusible links

-

Fusing temperature

72°C.

Guidance for specification option:

As standard.

104°C.

147°C.

Spare fusible links

-

Manufacturer guidance

Insert requirements or omit.

Design

Round duct flange (P).

Round duct flange and installation brackets (PK).

Spiro damper (SL).

Spiro damper, with installation brackets (SK).

Actuator

Manual.

Diameter

200 mm.

225 mm.

250 mm.

280 mm.

300 mm.

Show more

Length

300 mm.

500 mm.

Duct connection

Mandik FFDM breakaway joint.

Guidance for specification option:

FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained.

Refer to FFDM – Technical specifications for options and insert requirements.

Breakaway joint (supplied by others).

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Breakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper.

Sustainability data

Country of product manufacture

Czechia

Material

Steel

Calcium silicate

Third party certifications

Third party certifications

DoP

DoP

FDMR 180 – Declaration of performance

Certificate of constancy of performance

Certificate of constancy of performance

FDMR 180 – Certificate

EPD

EPD

Environmental Product Declaration - Fire Dampers

Literature

FDMR 180 – Technical specifications (148/21)

FDMR 180 – Technical specifications (148/21)

FFDM – Technical specifications (137/19)

FFDM – Technical specifications (137/19)

Similar products from Mandik UK Limited

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised  - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm)  - Manual/Motorised - Fire Damper

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper