NBS Source
I'm a manufacturer
Compare variants

Legrand Floor Trunking Systems

Verified by manufacturer 3 days ago

Chequer Plate Floor Trunking

Legrand Electric Ltd Variant:

A range of flush and in-screed cable management floor systems.

Jump to:
0345 605 4333 Website

Application

Suitable for commercial and industrial applications.

Description

A range of flush and in-screed cable management floor systems.

The range includes: Flush Floor Trunking, Shallow Flush Floor Trunking, Underfloor Duct, Commercial Floor Trunking Recessed & Flush, Chequer Plate Floor Trunking and associated floor boxes and accessories.

Flush Floor Trunking is suitable for distributing power, data and communication in any commercial environment. It can be used if service outlets are required. Cables can be accessed after installation has been completed. Floor boxes can be positioned at any point along the trunking and removed and repositioned at a later date.

Shallow Flush Floor Trunking is designed to distribute power, data and communication where the amount of screed that can be removed is limited. It can be used if service outlets are required. Cables can be accessed after installation has been completed.

Underfloor Duct is installed under the screed, providing a strong yet cost-effective solution. The position of service outlets and junction boxes is fixed before installation. Service outlets and junction boxes are height-adjustable to fit flush with the screed.

Features and benefits:

  • All outlet systems are designed to accept a wide range of mix-and-match lids and trims.
  • Bespoke metal trims are available in any RAL reference to suit a building’s design scheme.

General information

Color

Grey

Other

Finish

Galvanized

Powder-coated

Material

Steel

Shape

Rectangle

Length

2000 mm

Width

370 mm

150 mm

225 mm

300 mm

100 mm

Height

Warranty description

Two year

Uniclass

Pr_65_70_11_31 Floor-mounted cable trunking and ductingPrimary

CAWS

P31/300 Floor ducting/ trunking

SKU Code

FFO, AFS, AFU, FF, FRL, FTP

Specification data - Floor-mounted cable trunking and ducting

Classification data

Standards

To BS EN 61534 and BS EN 50085.

Resistance to impact

2 J.

Temperature properties

-

Storage and transport temperature (minimum)

-25°C.

Installation and application temperature (minimum)

-15°C.

Application temperature (maximum)

+60°C.

Resistance to flame propagation

Non-flame-propagating.

Electrical properties

With electrical continuity characteristics. Without electrical insulating characteristics.

Sizes

100 x 50 mm.
150 x 75 mm.
300 x 100 mm.

Manufacturer guidance

  • Standard lengths: body 2.0 m, lid 1.0 m.
  • Standard lid thickness: 6.5 mm.
  • Chequer plate floor trunking is available in single compartment as standard complete with lid, all necessary connectors and screws.
  • Internal dividers are fitted on all trunking lengths 225 mm and above to provide lid support.

Compartments

Three.
Four.

Accessories and fittings

-

Generally

Factory-made by the cable trunking or ducting manufacturer and of the same material type and finish as the cable trunking or ducting.

Types

90° riser bend.

Guidance for specification option:

Supplied with screeding cover. Provides conduit entry with 20 mm knockouts.

End stop.
Junction box.

Guidance for specification option:

Supplied with connectors and blanking plates. To be configured as a fourway, tee, bend or straight through connector box.

Material/ Finish

Body: Pre-galvanized sheet steel to BS EN 10346.
Lid: Mild steel, powder-coated grey 18B25.

Guidance for specification option:

Other colours available to special order.

Sustainability data

Material

Steel