NBS Source
I'm a manufacturer

PROMATECT-250® - 2 Sided Column Protection up to 600 mm x 600 mm. Board fix to Angle, Z section fix to Column - ST P250-043S

Verified by manufacturer 2 months ago

Promat UK Product certifications:
  • UL-EU Certified

    UL-EU Certified

    Certificate type

  • EPD

    EPD

    Certificate type

Encasement system using non-combustible mineral bound light weight boards. Two-sided column protection up to 600 x 600 mm; board fix to angle, Z-section fix to column.

Jump to:
0800 145 6033 Website

Application

Steelwork protection.

Description

PROMAT PROMATECT®-250 is a non-combustible mineral bound light weight board and provides a high degree of strength and dimensional stability and fire protection to structural steel and is suitable for areas where the relative humidity is up to 85%.


It is classified A1 non-combustible according to BS EN 13501-1. 


Features and benefits:

  • Two-sided column protection up to 600 x 600 mm.
  • Board fix to angle, Z-section fix to column.
  • PROMATECT®-250 comprises autoclaved calcium silicate spheres (PROMAXON® is a synthetic hydrated calcium silicate in spherical form) bound in a mineral matrix.
  • Off-white in colour.
  • One face is smooth and ready to form a finished surface, able to receive almost any form of architectural/finish treatment.
  • The reverse face is sanded.

General information

Color

White

Finish

Smooth

Guidance for specification option:

One face, ready to form a finished surface.

Sanded

Guidance for specification option:

Reverse face.

Material

Calcium silicate

Guidance for specification option:

Autoclaved calcium silicate spheres bound in a mineral matrix.

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

-

Manufacturer guidance

Etex Building Performance Limited warrants that its products and component parts shall be durable and free from defects due to faulty manufacturing or factory workmanship. Etex Building Performance Limited also warrants that, when combined to form a system as detailed in the Project Pack specification document including associated CAD drawings and any other specific technical recommendations made in relation to this project, will meet the specified system performance. The full details of this warranty are covered in the Promat Warranty Document, available upon request.

Uniclass

Ss_25_25_45_68 Rigid sheet casing systemsPrimary

CAWS

K11/54 Fire protection board

K11/885 Fire protection board

Specification data - Rigid sheet casing systems

Classification data

Support

Metal angle 50 x 25 x 0.5 mm, Z-section 25 x 25 x 25 x 1.2 mm.
Fixings: 3.7 x 16 mm shot-fire nails or M4.2 x 12 mm wafer head screws.

Guidance for specification option:

Casings are installed using metal angles fixed to the steel flange, for SHS/ RHS and PFC beams angles fixed to the wall. Additional Z-section is fixed to the opposite flange (or face, for SHS/ RHS and PFC) to support flange boards, running parallel to the wall.


Fixings: maximum 300 mm centres.

Insulation

Low density (10–30 kg/m³) glass mineral wool.

Guidance for specification option:

If required for acoustic or thermal performance.

Not required.

Linings

Inner and outer layers: PROMATECT®-250 board thickness determined by section factor (A/V), fire resistance period and limiting steel temperature.

Guidance for specification option:

Note: compartmentation not applicable for this encasement design.

Manufacturer guidance

  • Boards can be left untreated or painted; where decorative finish is required, see Colour/ finish below.
  • Board to board joints on adjacent sides are staggered by a minimum 530 mm.
  • Board thicknesses over 25 mm are installed as a double layer.

Fasteners

Fixing to metal angle: M4 CSK Self Tapping Screws.
Fixing to board edge: Chisel point staples minimum 35 x 12 x 1.6 mm (50 x 12 x 1.6 mm for board thicknesses over 15 mm).

Guidance for specification option:

  • Fixing to metal angle: Maximum 200 mm centres. Screw length to provide minimum penetration of 10 mm through the angle.
  • Fixing to board edge and coverstrips: Maximum 150 mm centres. End staples are located nominally 40 mm from the corner of the board.

Manufacturer guidance

See also Installation below.

System accessories

FSi Promat Pyrocoustic® Fire Resistant Sealant.

Fire resistance

Guidance for specification option:

Fire resistance (minutes) to EN 13501-2. Insert requirements.

Colour/ Finish

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Decorative finishes should be applied in accordance with Promat Technical Data Sheet TDS 056 (https://www.promat.com/en-gb/construction/documentation/).

Section factor

Maximum 350 m-1.

Steel sections

Up to 600 x 600 mm.

Strips

Thickest encasement board layer x 100 mm wide PROMAT PROMATECT®-250 coverstrips fitted at the head and base of the column.

Guidance for specification option:

  • Coverstrips are optional behind board joints.
  • Coverstrips are not required to the flanges of column encasements.

Third-party certification

As detailed in UL-EU Certificate No. UL-EU-01220a-CPR.

Guidance for specification option:

Note: Depending on site conditions, alternative fixing methods may be required for beams and columns, one- or two-sided exposure or interface with other building elements. These fixing methods are outside the scope of current EN test methods.

These recommendations are based on the principles of EN 13381-4 and given in good faith. They should be approved by the responsible designer or through independent third party assessment.

Installation

A nominal 3 mm gap must be left between the edge of the PROMAT PROMATECT®-250 board and the solid wall. This gap must be filled with FSi Promat Pyrocoustic® Fire Resistant Sealant.

Sustainability data

Country of material origin

Belgium

Country of product manufacture

Belgium

Manufacturer guidance

Applies to the bulk board material only. Other components are from other countries. Consult manufacturer for details.

Material

Calcium silicate

Guidance for specification option:

Autoclaved calcium silicate spheres bound in a mineral matrix.

Recyclability

Gypsum, calcium silicate and metal components can be recycled depending on the segregation of all materials.

Product certifications

Product certifications

UL-EU Certified

UL-EU Certified

UL-EU-01220 Promatect-250 Steel Protection

EPD

EPD

EPD - Promat PROMATECT-250

Literature

Promat Passive Fire Protection for Structural Steel

Promat Passive Fire Protection for Structural Steel

Similar products from Promat UK

Promat PROMATECT®-XS Structural Steel Protection ST PXS-005S - Three Sided Beam Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-005S - Three Sided Beam Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-006S - Three Sided Column Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-006S - Three Sided Column Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-007S - Four Sided Beam Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-007S - Four Sided Beam Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-008S - Four Sided Column Encasement System

Promat PROMATECT®-XS Structural Steel Protection ST PXS-008S - Four Sided Column Encasement System

Promat VERMICULUX®-S - Encasements - ST VLUX-209S

Promat VERMICULUX®-S - Encasements - ST VLUX-209S

Promat VERMICULUX®-S - Encasements - ST VLUX-210S

Promat VERMICULUX®-S - Encasements - ST VLUX-210S

Promat VERMICULUX®-S - Encasements - ST VLUX-213S

Promat VERMICULUX®-S - Encasements - ST VLUX-213S

Promat VERMICULUX®-S - Encasements - ST VLUX-214S

Promat VERMICULUX®-S - Encasements - ST VLUX-214S

Promat VERMICULUX®-S - Encasements - ST VLUX-215S

Promat VERMICULUX®-S - Encasements - ST VLUX-215S

Promat VERMICULUX®-S - Encasements - ST VLUX-216S

Promat VERMICULUX®-S - Encasements - ST VLUX-216S